oventrop R-Tronic RT B Installation And Operating Instructions Manual page 59

Climate display device/control
Table of Contents

Advertisement

Display notes and error messages
RADIO DISTURBANCE
or
COMMUNICATION ERROR
NOT AVAILABLE
ENOCEAN ERROR
INIT ERROR
MEMORY DEFECTIVE
TEMP SENSOR DEFECT
HUMIDITY SENS DEFECT
CO2 SENSOR DEFECT
HIGH PPM
BUTTON DEFECTIVE
NOTE
If you do not succeed in eliminating the malfunction, disconnect the "R-Tronic" and
the actuator "AKTOR MH/MD CON B" from the power supply (battery or power pack)
for about 10 seconds. A restart will help to solve the problem in many cases.
If the problem could not be solved, restore the factory settings of the "R-Tronic" and
of the actuator as described in chapter 5 (paragraph 4.9).
If that still does not help, please contact your specialist heating company or the
company Oventrop.
Radio communication disturbed
Error analysis via INFORMATION
► DIAGNOSIS (see also chapter 4.1).
No status message from the window contact
(accessory) within 24 hours
No status message from the window contact within
one hour
Possible error at installed wireless module
Initialization error occurred.
Error in the electronic memory ("R-Tronic")
Temperature sensor defective ("R-Tronic" or Aktor).
Humidity sensor in the "R-Tronic TF/TFC" defective.
CO
sensor in the "R-Tronic TFC" defective.
2
CO
value higher than 2.000 PPM
2
Button at the "R-Tronic" does not trigger a function
(contact problem)
- 59 von 64 -