SECTION 2 - OPTIVIEW OPERATION
Condenser Refrigerant Temperature
This display indicates the temperature of the refriger-
ant in the condenser provided by RT17. Will only be
displayed if the sensor is enabled. This sensor is part of
the optional refrigerant sensor kit.
Condenser Liquid Flow Switch (Open/Closed)
This display will indicate the flow switch is "closed"
when condenser liquid flow is present.
Condenser Liquid Pump (Run/Stop)
Indicates the operating status of the condenser liquid
pump.
PROGRAMMABLE
Drop Leg (Enabled / Disabled)
Access Level Required: SERVICE
The drop leg sensor must be enabled to utilize the re-
frigerant temperature sensor output on Trane chillers.
Should be enabled for Trane applications where the
optional refrigerant sensor kit is installed.
Condenser Refrigerant Temperature
(Enabled/Disabled)
Access Level Required: SERVICE
This condenser refrigerant temperature must be en-
abled to utilize the refrigerant temperature sensor out-
put on Trane chillers. Should be enabled for Trane ap-
plications that have the optional refrigerant sensor kit
installed.
Purge Type
Access Level Required: SERVICE
Allows for selection of type of purge system. If a Trane
purge unit is utilized, "Skyguard Remote" must be se-
lected.
28
NAVIGATION
Home
Access Level Required: VIEW
Returns display to the Home screen.
Purge Control
Access Level Required: VIEW
Advances to a sub-screen which allows programming
of the purge system setpoints. Only displayed if the
OptiView Control Center is configured for the YORK
TurboGuard II Purge System.
FORM 160.10-O1
ISSUE DATE: 4/27/2018
JOHNSON CONTROLS