FORM 160.10-O1
ISSUE DATE: 4/27/2018
YORK SETPOINTS
CHILLER ID 0
(c) 1997 – 2004 YORK INTERNATIONAL CORPORATION
Mon 22 Nov 2004 8:48:27 AM
Software Versions
-----------------------------------------------------
Controls
BIOS
Kernel
GUI
SIO
GPIC
Ext I/O
VSD [Not displayed if Motor Type is not VSD]
SSS [Not displayed if Motor Type is not Mod B SSS]
System Information
-----------------------------------------------------
System Language
Data Display Mode
Control Source
Remote Analog Input Range
Clock
Jumper Settings
-----------------------------------------------------
Oil Pump Type
Coastdown
Chilled Liquid Pump Operation
Refrigerant Selection
Anti-Recycle
Power Failure Restart
Liquid Type
Motor Type
Printer Setup
-----------------------------------------------------
Automatic Printer Logging
Log Start Time
Output Interval
Printer Type
Baud
Data Bits
Parity
Stop Bits
COM 2 Setup
-----------------------------------------------------
Baud
Data Bits
Parity
Stop Bits
Evaporator
-----------------------------------------------------
Leaving Chilled Local Setpoint
Leaving Chilled ISN Setpoint
Leaving Chilled Modem Setpoint
Leaving Chilled Analog Setpoint
Leaving Chilled Digital Setpoint
Remote Range
Sensitivity
FIGURE 52 - SAMPLE PRINTOUT (SETPOINTS)
JOHNSON CONTROLS
Restart Offset
Restart Setpoint
Shutdown Offset
Shutdown Setpoint
Brine Low Evaporator Cutout
Smart Freeze
Refrigerant
= C.MLM.08.01
Condenser
= C.MLM.00.03
-----------------------------------------------------
= 0.18
High Pressure Warning Threshold
= 0.33
Drop Leg
= 0.22
= 0.04
Oil Sump
= 0110112091996
-----------------------------------------------------
= C.VSD.00.00
Manual Pump
= C.SSS.01.01
Low Pressure Limit
Prelube Time
Coastdown Time
= English
= English
Purge Control
= Local
-----------------------------------------------------
= 0–10 Volts
High Efficiency
= Enabled
Maximum Purge / Hour
[Following section not displayed if Hot Gas Bypass is not enabled]
Hot Gas
= Standard
-----------------------------------------------------
= Standard
Hot Gas
= Standard
Hold Period
= R123
Close Percentage
= Enabled
= Auto
= Water
[Following section not displayed if Level Control is not enabled]
= Fixed Speed
Refrigerant Level Control
-----------------------------------------------------
Level Control
Setpoint
= Disabled
Period
= 12:00 am
Proportion Limit Open
= 60 Min
Proportion Limit Close
= Okidata
Rate Limit Open
= 9600 Baud
Rate Limit Close
= 8 Bits
= None
[Not displayed if Motor Type is not EM]
= 1 Bit
Electro-Mechanical Starter
-----------------------------------------------------
Local Motor Current Limit
= 19200 Baud
Remote ISN Current Limit
= 8 Bits
Remote Analog Current Limit
= Odd
Remote Digital Current Limit
= 1 Bit
Remote Modem Current Limit
Pulldown Demand Limit
Pulldown Demand Time
= 45.0 ºF
= 45.0 ºF
= 45.0 ºF
FIGURE 52 - SAMPLE PRINTOUT (SETPOINTS)
= 45.0 ºF
(CONT'D)
= 45.0 ºF
= 10.0 ºF
= 100%
SECTION 4 - PRINTERS
= 0.0 ºF
= 45.0 ºF
= 4.0 ºF
= 41.0 ºF
= 12.5 Psig
= Off
= Enabled
= 28.8 Psig
4
= Enabled
= Disabled
= 15.0 PSID
= 30 Sec
= 150 Sec
= Off
= 20
= Enabled
= 30 Min
= 5 %
= On
= 50 %
= 3.5 Sec
= 15 %
= 45 %
= 10 %
= 10 %
= 100 %
= 100 %
= 100 %
= 100 %
= 100 %
= 100 %
= 0 Min
129