APPENDIX B - PROGRAMMABLE SETPOINT VALUES
TABLE 13 - PROGRAMMABLE SETPOINT VALUES
EVAPORATOR SCREEN
SETPOINT
Local Leaving Chilled Liquid Temperature - Setpoint
Local Leaving Chilled Liquid Temperature - Range
LCHLT Cycling Offset - Shutdown
LCHLT Cycling Offset - Restart
Brine Low Evaporator Cutout
Sensitivity
Smart Freeze
Refrigerant (Sensor)
LOAD RATE SCREEN (EVAPORATOR SUBSCREEN)
SETPOINT
Load Rate
Sensitivity
Pulse Time
Pulse Period
CONDENSER SCREEN
SETPOINT
High Pressure Warning Threshold
Drop Leg (Sensor)
Refrigerant (Sensor)
Purge Type
PURGE SCREEN (CONDENSER SUBSCREEN)
SETPOINT
High Efficiency Purge System
Maximum Purges / Hour
Maximum Purges / Hour
JOHNSON CONTROLS
ACCESS
MINIMUM
LEVEL
VALUE
38.0 °F - Water
Operator
36.0 °F - Sm Frz
10.0 °F - Brine
Operator
10.0 °F
Operator
1.0°F
Operator
0.0 °F
Service
0.0 PSIA
Service
10 %
Service
Off
Service
Disabled
ACCESS
MINIMUM
LEVEL
VALUE
0.38 °F / Min, 0.75°F / Min, 1.13 °F /
Service
Min, 1.50 °F / Min, 2.25 °F / Min, 3.00°F
/ Min, 5.25°F / Min, 10.50 °F / Min
Service
10%
Service
0.1 Secs
Service
0.0 Secs
ACCESS
MINIMUM
LEVEL
VALUE
Service
14.0 PSIA
Service
Disabled
Service
Disabled
TurboGuard, SkyGuard Local,
Service
SkyGuard Remote
ACCESS
MINIMUM
LEVEL
VALUE
Service
Disabled
Operator
10
Service
1
MAXIMUM
DEFAULT
VALUE
70.0 °F
45.0 °F
20.0 °F
10.0 °F
Varies with
4.0 °F or highest
LCHLT setpoint
allowed value,
and chilled liquid
whichever is
type.
lower.
Varies with
LCHLT setpoint
0.0 °F
and chilled liquid
type.
12.5 PSIA
12.5 PSIA
200 %
100 %
On
Off
Enabled
Disabled
MAXIMUM
DEFAULT
VALUE
0.38 °F / Min
200%
100%
10.0 Secs
0.1 Secs
10.0 Secs
2.0 Secs
MAXIMUM
DEFAULT
VALUE
28.8 PSIA
28.8 PSIA
Enabled
Disabled
Enabled
Disabled
SkyGuard
Remote
MAXIMUM
DEFAULT
VALUE
Enabled
Disabled
30
20
30
20
B
133