Output Electrical Specifications; System Electrical Specifications - Huawei UPS5000-E Series User Manual

Hide thumbs Also See for UPS5000-E Series:
Table of Contents

Advertisement

UPS5000-E-(20 kVA-160 kVA)
User Manual (Low voltage)
Item
sharing
Charge voltage

8.7 Output Electrical Specifications

Item
Output system
Voltage
Frequency
Total harmonic
distortion of
output voltage
(THDv)
Output PF
Transfer time
Output voltage
unbalance
Overload
capability

8.8 System Electrical Specifications

Item
Issue 03 (2020-04-27)
UPS5000-E-60K-F60
battery strings are shared.
Equalized voltage: 2.35 V/cell
Float voltage: 2.25 V/cell
UPS5000-E-60K-F60
Three-phase, five-wire
208 V AC, 220 V AC, or 230 V AC (tolerance ± 1%)
In normal mode, the mains frequency is synchronized with the bypass
input frequency.
In battery mode, the frequency is 50 Hz or 60 Hz (tolerance ± 0.25%).
< 2% (full linear load); ≤ 5% (full non-linear load)
1
0 ms
Voltage unbalance: ± 3%; phase unbalance: ± 2°
Inverter overload capability:
105% < load < 110%: transfer to bypass mode after 60 min
111% < load ≤ 125%: transfer to bypass mode after 10 min
125% < load ≤ 150%: transfer to bypass mode after 1 min
Bypass overload capability:
Load ≤ 135%: run continuously at 30°C or lower
1000% load: run for 100 ms
UPS5000-E-60K-F60
Copyright © Huawei Technologies Co., Ltd.
UPS5000-E-100K
-F100
UPS5000-E-100K
-F100
UPS5000-E-100K-F10
0
8 Technical Specifications
UPS5000-E-160K
-F160
UPS5000-E-160K
-F160
UPS5000-E-160K-F
160
198

Advertisement

Table of Contents
loading

Table of Contents