UPS5000-E-(20 kVA-160 kVA)
User Manual (Low voltage)
Figure 3-17 Securing the antiseismic kits to the floor
----End
3.2.3.2 Installing an IP21 Component
Procedure
Step 1 Install leveling feet at the bottom of the IP21 component, with two long feet on the front and
two short feet at the rear.
Figure 3-18 Installing leveling feet
Step 2 Secure the IP21 component to the top of each cabinet using four M12 screws.
Issue 03 (2020-04-27)
Refer to the "front" and "back" silk screens on the surface of the IP21 component.
Select the mounting holes for leveling feet based on the cabinet width onsite.
Copyright © Huawei Technologies Co., Ltd.
3 Installation
56