Huawei UPS5000-E Series User Manual page 136

Hide thumbs Also See for UPS5000-E Series:
Table of Contents

Advertisement

UPS5000-E-(20 kVA-160 kVA)
User Manual (Low voltage)
Item
Table 4-15 Bypass settings
Item
BPM mode
upon BPM
overtemp.
Lightload
BPM cur. eql.
detect
Battery
Battery parameter settings impact battery maintenance, battery lifespan, and UPS discharge
time. When you set battery parameters, note the following:
Issue 03 (2020-04-27)
Description
determines that the inverter
capacitor is faulty, it shuts down
the inverter to prevent the fault
from expanding.
Description
Specifies whether to start bypass
mode when overtemperature
occurs.
Enable or disable the light load
bypass current imbalance alarm.
If this parameter is set to Enable,
the load is light (less than 30%
load), and the load rate of a
certain rack is less than 10%, the
system will generate a bypass
current imbalance alarm and
cannot enter the ECO mode. If
this parameter is set to Disable,
the preceding detection is not
performed. Whether the bypass
current is imbalanced does not
affect the ECO bypass mode.
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
Default Value
Value Range
Enable
Disable, Enable
Enable
Disable, Enable