UPS5000-E-(20 kVA-160 kVA)
User Manual (Low voltage)
Component
component
Top outlet kit
Top entry
cabinet
Dry contact
extended card
Backfeed
protection card
BMU
Ambient
temperature
and humidity
sensor
Parallel cable
BSC cable
Issue 03 (2020-04-27)
Model
N/A
N/A
N/A
N/A
N/A
N/A
5 m, 10 m, or 15 m
5 m, 10 m, 15 m or 60 m
The ECM extended subrack does not support onsite installation. If you require this optional component,
inform Huawei when you purchase the UPS. Huawei installs it before delivery.
Copyright © Huawei Technologies Co., Ltd.
Function
the cabinet, protecting the cabinet to
IP21.
If you need to install the cabinet
against a wall, install a top outlet kit
to meet heat dissipation
requirements. The top outlet kit apply
only to the UPS5000-E-60K-F60 and
UPS5000-E-100K-F100.
Install a top entry cabinet to route
cables from the top of the
UPS5000-E-160K-F160 cabinet.
Provides extended monitoring ports:
five relay output ports and five input
ports.
Detects mains and bypass backfeed
and provides protection.
Monitors battery voltages and
temperatures as well as battery
string charge and discharge
currents.
Communicates with the UPS over
Modbus.
Ambient temperature and humidity
sampling board applicable to
batteries.
Connects UPSs in parallel.
Transmits bus synchronization
signals in a dual-bus system.
2 Overview