Set Single/Parallel after double check. Incorrect setting may affect the normal UPS
operation.
Output voltage level refers to the line voltage level. Set it based on site requirements.
Set Output frequency correctly; otherwise, loads may be affected and the UPS may not
work properly.
Battery parameter settings are critical to battery maintenance, battery lifespan, and UPS
discharge time.
Figure 5-1 Settings Wizard
Step 2 After you set parameters on the Settings Wizard screen, the system displays the Bypass
mode and No battery alarms, which do not need to be handled. If there is any other alarm,
you need to rectify the fault.
Issue 03 (2020-04-27)
Set the time and date correctly. Incorrect time and date will cause false fault analysis during
maintenance or repair.
After you set network parameters, connect the UPS to the network over a network cable, which
enables you to remotely manage the UPS. If you do not need remote management, retain the default
network parameter settings.
After you set parameters on the Settings Wizard screen, choose System Info > Settings > System
Setting. Check that System Capacity, Power module capacity, Requisite modules, and
Redundant modules match the actual values.