UPS5000-E-(20 kVA-160 kVA)
User Manual (Low voltage)
Step 5 Route the signal cables on the left side of subracks along the left side of the cabinet and the
cables on the right side of subracks along the right side of the cabinet, and then bind the
cables to the cabinet, as shown in
Figure 3-34 Connecting signal cables
----End
Issue 03 (2020-04-27)
Figure 3-33 Neutral wire
Single mains
For single mains, the copper bars between the mains and bypass input terminals do not
need to be removed, and bypass input cables do not need to be connected.
The number and colors of signal cables in
Copyright © Huawei Technologies Co., Ltd.
Figure
3-34.
Figure 3-34
are for reference only.
3 Installation
69