3.2.6 Routing Cables (160 kVA)

3.2.6.1 Top Cable Routing

Context
Procedure
Step 1 Place the top entry cabinet on the left or right of the UPS based on actual requirements.
Step 2 Remove the right panel from the UPS and the front panel from the top entry cabinet, and put
the panel and screws away.
Step 3 Level the feet of the top entry cabinet to make it in the same plane with the UPS.
Step 4 Remove the top entry panel for the top entry cabinet and the cover for control cables, use a
hole saw to drill holes in the top entry panel, and reinstall the top cover on the top entry
cabinet.
Step 5 Install the connecting kit on the UPS. Combine the UPS and the top entry cabinet by using a
connecting kit.
Issue 03 (2020-04-27)
Before using a top entry cabinet for cable routing, determine whether to place the top entry
cabinet on the left or right of the UPS5000-E cabinet.
After routing cables, use sealing putty to fill in the gap between the cables and the cabinet.
If you choose to route cables by drilling holes, paste grommet strip to the hole edge to protect cables.