Huawei UPS5000-E Series User Manual page 34

Hide thumbs Also See for UPS5000-E Series:
Table of Contents

Advertisement

UPS5000-E-(20 kVA-160 kVA)
User Manual (Low voltage)
Figure 2-10 ECM
Table 2-2 Ports on the ECM
Silk Screen
PARALLEL
BSC
Table 2-3 Indicator description
Indicator
NORMAL
ALM
FAULT
Issue 03 (2020-04-27)
Description
The PARALLEL port transmits parallel signals between racks.
The BSC port is used in a dual-bus system to synchronize output
frequencies and phases between UPS systems, ensuring that two buses
can switch with each other.
BSC cables are hot-swappable.
For a single UPS, the parallel cable is not needed.
Color
Green
Yellow
Red
Copyright © Huawei Technologies Co., Ltd.
Status
Description
Steady on
This ECM is the active ECM.
Blinking at 0.5
This ECM is the standby ECM and it is ready.
Hz
Off
This ECM is not ready or the software of this
ECM is being upgraded.
Blinking at 4
The software of the ECM is being upgraded or
Hz
not configured.
Steady on
The ECM has a minor alarm, but it does not
need to be replaced.
Off
The ECM has no minor alarm or the software
of the ECM is being upgraded.
Steady on
The ECM has a critical alarm.
Off
The ECM has no critical alarm or the software
of the ECM is being upgraded.
2 Overview
26