Output Electrical Specifications - Huawei UPS5000-E User Manual

Hide thumbs Also See for UPS5000-E:
Table of Contents

Advertisement

UPS5000-E-(400 kVA-800 kVA)
User Manual (50 kVA Power Modules)
Item
One-button cold start
Charger output power
Charger current limit
Battery string sharing
Charging voltage
(lead-acid battery)

9.8 Output Electrical Specifications

Item
Output system
Voltage
Frequency
Total harmonic
distortion of
output voltage
(THDv)
Output PF
Transfer time
Output voltage
unbalance
Issue 17 (2023-07-10)
400 kVA
Three-phase, four-wire, and PE
380 V AC, 400 V AC, or 415 V AC (tolerance ± 1%) (line
voltage)
● In normal mode, the mains frequency is synchronous with
the bypass input frequency.
● In battery mode, the frequency is 50 Hz or 60 Hz (tolerance
±0.05%).
● ≤ 1% (100% linear load)
● ≤ 4% (100% non-linear load)
1
● 0 ms (uninterruptible transfer)
● ≤ 20 ms (interruptible transfer)
Voltage unbalance: ±3%; phase unbalance: ±2°
Copyright © Huawei Digital Power Technologies Co., Ltd.
Specifications
In the case of a mains failure, batteries can start the
UPS to power loads.
Under rated conditions, the maximum charge power of
a module is 5 kW.
Maximum 10 A for a module
Battery string sharing is supported in a parallel system.
No battery string is shared by default.
● Equalized charge voltage: 2.3–2.4 V/cell, default:
2.35 V/cell (30–42 batteries)
● Equalized charge voltage: 2.3–2.4 V/cell, default:
2.35 V/cell (44 batteries)
● Float charge voltage: 2.23–2.3 V/cell, default: 2.25
V/cell (30–44 batteries)
500 kVA
9 Technical Specifications
800 kVA
600 kVA
209