Huawei UPS5000-E Series User Manual page 135

Hide thumbs Also See for UPS5000-E Series:
Table of Contents

Advertisement

UPS5000-E-(20 kVA-160 kVA)
User Manual (Low voltage)
Item
Current equal.
detection
Inverter
async. alarm
Bus
overvoltage
recovery
Bus overvolt.
recovery time
Capacitor
failure
detection
Issue 03 (2020-04-27)
Description
Monitors the current differences
between racks or modules. If this
parameter is set to Enable, the
Mod. Cur. Eql. Data can be
viewed on the running
information screen.
Specifies whether an Inverter
asynchronous alarm can be
displayed on the LCD when the
inverter cannot track the bypass
frequency change. Normal power
supply is not affected no matter
whether this parameter is set to
Enable or Disable.
Specifies whether to
automatically clear the alarm and
restart the power module when
the rectifier or inverter shuts
down due to a bus overvoltage
alarm. If Bus overvoltage
recovery is set to Enable, the
bus overvoltage alarm is
automatically cleared, and the
rectifier and inverter
automatically start when the bus
voltage recovers within Bus
overvolt. recovery time. When
Bus overvoltage recovery is set
to Disable, the bus overvoltage
alarm cannot be automatically
cleared, and the rectifier and
inverter cannot automatically
start.
If Bus overvoltage recovery is
set to Enable, the bus
overvoltage alarm is
automatically cleared, and the
rectifier and inverter
automatically start when the bus
voltage recovers (less than 420
V) within Bus overvolt.
recovery time.
If Capacitor failure detection is
set to Enable, the power module
(power unit) performs inverter
capacitor fault detection based on
the settings of Capacitor failure
detection upper limit and
Capacitor failure detection
lower limit. If the power module
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
Disable
Disable, Enable
Disable
Disable, Enable
Enable
Disable, Enable
5s
5s, 1 min, 5 min,
10 min
Disable
Disable, Enable
127