UPS5000-E-(20 kVA-160 kVA)
User Manual (Low voltage)
Item
Altitude
Noise
8.3 Safety Regulations and EMC
Item
Safety
regulations
EMC
8.4 Mains Input Electrical Specifications
Item
Input system
Rated input
voltage
Issue 03 (2020-04-27)
UPS5000-E-60K-F
60
1000–4000 m
When the altitude is above 1000 m, the load that the UPS can support
decreases by 1% for each additional 100 m.
At atmospheric pressure (25° C)
50% load: 60 dB
75% load: 63 dB
100% load: 68 dB
UPS5000-E-60K-F60
EN62040-1: 2008
IEC62040-1: 2008
YD/T2165-2010
GB/T14715-93
EN62040-2
IEC62040-2
IEC61000-3-11
IEC61000-3-12
IEC61000-2-2
IEC61000-4-2
EN61000-4-3
EN61000-4-6
IEC61000-4-8
IEC61000-4-11
UPS5000-E-60K-F60
Three-phase, five-wire
208 V AC, 220 V AC, or 230 V AC (line voltage)
Copyright © Huawei Technologies Co., Ltd.
UPS5000-E-100K-F
100
UPS5000-E-100K-
F100
UPS5000-E-100
K-F100
8 Technical Specifications
UPS5000-E-160K-F160
UPS5000-E-160K-
F160
UPS5000-E-160
K-F160