UPS5000-E-(20 kVA-160 kVA)
User Manual (Low voltage)
Item
Battery
Nominal discharge current
input
(240 V current; twenty 12 V
batteries) (A)
Maximum discharge current
(end of discharge current of
twenty 12 V batteries, namely,
1.67 V/cell discharge current
for 120 2 V cells) (A)
Recommended
cross-sectional
2
area (mm
)
Ground
Recommended
cable
cross-sectional
2
area (mm
)
Table 3-4 Power cable connector requirements for the UPS5000-E-60 kVA and UPS5000-E-100 kVA
Connector
Mains input connector
Issue 03 (2020-04-27)
UPS5000-E-60K-F60
20
kVA
al area of the
neutral
wire.)
110
131
+
3 x
35
N
-
PE
1 x
16
When selecting, connecting, and routing power cables, follow local safety regulations and rules.
If external conditions such as cable layout or ambient temperatures change, perform verification in
accordance with the IEC-60364-5-52 or local regulations.
The currents listed in the table are measured at a rated voltage of 208 V. If the rated voltage is 220 V,
multiply the currents by 0.95. If the rated voltage is 230 V, multiply the currents by 0.92.
If primary loads are non-linear loads, increase the cross-sectional areas of neutral wires 1.5–1.7 times.
When the mains input and bypass input share a power source, configure both types of input power
cables as mains input power cables. The cables listed in the table are used only when the following
requirements are met:
Cable routing mode: For the UPS5000-E-(20 kVA-160 kVA), route one layer of cables along ladders
or brackets in accordance with mode F in the IEC60364-5-52.
The ambient temperature is 30° C.
The AC voltage loss is less than 3%, and the DC voltage loss is less than 1%.
20–160 kVA: single- or multi-core 90° C soft power cable with a copper conductor.
The AC power cable is no longer than 30 m, and the DC power cable is no longer than 40 m.
Connection Mode
Crimped OT terminals
Copyright © Huawei Technologies Co., Ltd.
UPS5000-E-1
00K-F100
40
60
80
kVA
kVA
kVA
219
329
439
263
394
525
3 x
2 x
2 x (3
95
(3 x
x 95)
70)
1 x
1 x
1 x 70
25
50
Bolt Type
M10
3 Installation
UPS5000-E-160K-F16
0
100
120
140
kVA
kVA
kVA
548
658
768
657
788
919
2 x (3
2 x (3
2 x (3
x
x
x
150)
120)
150)
1 x
1 x
1 x
95
95
95
Bolt Hole
Torque
Diameter
10.5 mm
26 N· m
160
kVA
877
1051
2 x (3
x 185)
1 x
120
43