(M) Item and output signal for monitoring

Purpose
To change the item monitored on the
operation panel
To assign functions to the output
terminals
To detect the control circuit
temperature
5.4.1
Monitor item selection on operation panel or via
communication
The item to be monitored on the screen of the operation panel can be selected. Install the operation panel of the inverter on
the converter unit.
Pr.
Name
774
Operation panel monitor
M101
selection 1
775
Operation panel monitor
M102
selection 2
776
Operation panel monitor
M103
selection 3
992
Operation panel setting dial
M104
push monitor selection
170
Watt-hour meter clear
M020
563
Energization time carrying-
M021
over times
268
Monitor decimal digits
M022
selection
891
Cumulative power monitor
M023
digit shifted times
290
Monitor negative output
M044
selection
 Monitor item list (Pr.774 to Pr.776, Pr.992)
• Use Pr.774 to Pr.776, or Pr.992 to select the item to monitor on the operation panel (FR-DU08).
• Refer to the following table and select the item to be monitored. The value in the Pr. setting column is set in each of the
parameters for monitoring (Pr.774 to Pr.776, and Pr.992) to determine the monitor item. The value in the RS-485 column
is used for the RS-485 communication special monitor selection. The value in the MODBUS RTU column is used for the
MODBUS RTU real time monitor. (The items marked with "—" cannot be selected. The circle in the [-] column indicates
that the indication of negative signed numbers is available.)
Parameter to set
Operation panel monitor item
selection, clearing the
cumulative value during
monitoring
Output terminal function
assignment
Control circuit temperature
monitoring
Initial value
Setting range
9999
(converter output
voltage)
9999
2, 8, 13, 20, 25,
(input current)
43, 44, 55, 62,
98, 9999
9999
(electronic
thermal O/L relay
load factor)
8
2, 8, 13, 20, 25,
(converter output
43, 44, 55, 62,
voltage)
98
0
10
9999
9999
(0 to 65535)
0
(Read-only)
0
9999
1
9999
0 to 4
9999
9999
0
0, 2, 4, 6
Pr.170, Pr.268,
P.M020 to P.M023,
Pr.290, Pr.563,
P.M044, P.M100 to
Pr.774 to Pr.776,
P.M104
Pr.891, Pr.992
P.M400 to P.M405
Pr.190 to Pr.195
P.M060
Pr.663
Description
The converter output voltage, input current and electronic
thermal relay function load factor monitor that are displayed
in monitor mode on the operation panel can be switched to
a specified monitor.
Select the monitor item displayed on the operation panel at
the time when the setting dial is pressed.
Set "0" to clear the watt-hour meter.
Set "10" to monitor the cumulative power in the range of 0 to
9999 kWh via communication.
Set "9999" to monitor the cumulative power in the range of
0 to 65535 kWh via communication.
The number of times that the cumulative energization time
exceeded 65535 hours is displayed. Read-only.
Value is displayed in 1 increments (an integer).
Value is displayed in 0.1 increments.
Function disabled.
Set the number of places the decimal point on the watt-hour
meter is shifted to left.
The meter stops at the maximum number.
The function of moving the decimal point is not available.
The readout is reset to 0 when it exceeds the upper limit.
Set the availability of output with a minus sign for the
operation panel display or monitoring via communication.