Terminal Block - Mitsubishi Electric FR-CC2-N Series Instruction Manual

Converter unit
Table of Contents

Advertisement

2.7.2
RS-485 terminal block
 Communication operation
Conforming
standard
Transmission
format
Communication
speed
Overall length
Connection cable
The RS-485 terminals enable communication operation from a personal computer, etc. When the PU connector is used for
connection between the converter unit and a personal, FA, or other computer with a communication cable, a user program can
run to monitor the converter unit or read and write parameters.
Communication can be performed with the Mitsubishi inverter protocol (computer link operation) and MODBUS RTU protocol.
For the details, refer to
Terminating resistor switch
Initially-set to "OPEN".
Set only the terminating resistor switch of
the remotest converter unit to the "100 Ω" position.
P5S
SG
(VCC)
(GND)
OPEN
VCC
GND
VCC
GND
100Ω
P5S
SG
(VCC)
(GND)
NOTE
• To avoid malfunction, keep the RS-485 terminal wires away from the control circuit board.
50
2. INSTALLATION AND WIRING
2.7 Communication connectors and terminals
EIA-485 (RS-485)
Multidrop link
Maximum 115200 bps
500 m
Twisted pair cable (4 pairs)
page
103.
SDA1
SDB1
RDA1
RDB1
(TXD1+)
(TXD1-)
(RXD1+)
(RXD1-)
+ TXD
-
+
RXD
-
+ TXD
-
+
RXD
-
SDA2
SDB2
RDA2
RDB2
(TXD2+)
(TXD2-)
(RXD2+)
(RXD2-)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-cc2-n450kFr-cc2-n630k

Table of Contents