 Specification of the applied 24 V external power supply
Item
Input voltage
Input current
Commercially available products (as of April 2019)
Model
Specifications: Capacity 50 W, output voltage 24 VDC, output current 2.2 A
*1
Installation method: Direct installation, screw type terminal block with cover
S8FS-G05024C
Input: Single-phase 100 to 240 VAC
Specifications: Capacity 60 W, output voltage 24 VDC, output current 2.5 A
*1
Installation method: DIN rail, push-in (spring) type terminal block
S8VK-S06024
Input: Single-phase 100 to 240 VAC
Specifications: Capacity 240 W, output voltage 24 VDC, output current 10 A
*1
Installation method: DIN rail, push-in (spring) type terminal block
S8VK-WA24024
Input: Three-phase 200 to 240 VAC
*1
For the latest information about OMRON power supply, contact OMRON corporation.
 Starting and stopping the 24 V external power supply operation
• Supplying 24 V external power while the main circuit power is OFF starts the 24 V external power supply operation.
Likewise, turning OFF the main circuit power while supplying 24 V external power starts the 24 V external power supply
operation.
• Turning ON the main circuit power stops the 24 V external power supply operation and enables the normal operation.
NOTE
• When the 24 V external power is supplied while the main circuit power supply is OFF, the converter unit operation is disabled.
• In the initial setting, when the main power supply is turned ON during the 24 V external power supply operation, a reset is
performed in the converter unit, then the power supply changes to the main circuit power supply.
 Confirming the 24 V external power supply input
• During 24 V external power supply operation, the ALARM LED of the accessory cover blinks. When the operation panel
(FR-DU08) is installed, "EV" blinks.
Blinking
POWER ALARM
• During 24 V external power supply operation, the 24 V external power supply operation signal (EV) is output. To use the
EV signal, set "68 (positive logic) or 168 (negative logic)" in any of Pr.190 to Pr.195 (Output terminal function selection)
to assign the function to the output terminal.
 Operation while the 24 V external power is supplied
• Fault records and parameters can be read and parameters can be written using the operation panel keys.
• During the 24 V external power supply operation, the monitor items and signals related to inputs to main circuit power
supply, such as input current and converter output voltage, are invalid.
• The alarms, which have occurred when the main circuit power supply is ON, continue to be output after the power supply
is changed to the 24 V external power supply. Perform the converter reset or turn OFF then ON the power to reset the
faults.
Rated specification
23 to 25.5 VDC
1.4 A or less
Product overview
Blinking
Manufacturer
OMRON Corporation
2. INSTALLATION AND WIRING
2.6 Control circuit
1
2
3
4
5
6
7
8
9
10
47

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-cc2-n450kFr-cc2-n630k

Table of Contents