Symbol
Name
(a)
Inverter (FR-A872)
(b)
Converter unit (FR-CC2-N)
(c)
Three-phase AC power supply
Molded case circuit breaker (MCCB),
(d)
earth leakage circuit breaker (ELB), or
fuse
(e)
Magnetic contactor (MC)
(f)
Noise filter
(g)
Noise filter
(h)
Induction motor
NOTE
• To prevent an electric shock, always earth (ground) the converter unit, the inverter, and the motor.
• Do not install a power factor correction capacitor, surge suppressor, or capacitor type filter on the inverter's output side. Doing
so will cause the inverter shut off or damage the capacitor or surge suppressor. If any of the above devices is connected,
immediately remove it. When installing a molded case circuit breaker on the output side of the inverter, contact the
manufacturer of the molded case circuit breaker.
• Electromagnetic wave interference:
The input/output (main circuit) of the inverter or the converter unit includes high frequency components, which may interfere
with the communication devices (such as AM radios) used near the inverter or the converter unit. To minimize interference,
enabling the built-in EMC filter or installing an external EMC filters is effective. (Refer to
• For details of options and peripheral devices, refer to the respective Instruction Manual.
2.1.2

Peripheral devices

 Compatible inverters
According to the connected motor capacity, configure the converter units and the inverters as follows.
• 690 VAC power input
Motor
Converter unit
capacity
FR-CC2-[]
(kW)
450
N450K
500
N500K
560
N560K
630
N630K
The life of the inverter and the converter unit is influenced by the
surrounding air temperature. The surrounding air temperature should be
as low as possible within the permissible range.
This must be noted especially when the inverter and the converter unit are
installed in an enclosure. Incorrect wiring may lead to damage of the
inverter and the converter unit.
The control signal lines must be kept fully away from the main circuit lines
to protect them from noise.
The built-in EMC filter of the converter unit can reduce the noise.
Must be within the permissible power supply specifications of the converter
unit.
Must be selected carefully since an inrush current flows in the converter
unit at power ON.
Install this to ensure safety.
Do not use this to start and stop the inverter. Doing so will shorten the life
of the inverter and the converter unit.
Suppresses the noise radiated from the power supply side of the converter
unit.
Install this to reduce the electromagnetic noise generated from the inverter
and the converter unit. The noise filter is effective in the range from about
0.5 to 5 MHz.
Connect a squirrel-cage induction motor.
Inverter
ND (normal duty, initial
SLD (superlight duty)
Model
Rated
Model
FR-A872-[]
current (A)
FR-A872-[]
05690
05690
569
06470
06470
647
07150
07150
715
Overview
page
55.)
value)
Rated
current (A)
512
569
647
2. INSTALLATION AND WIRING
Refer to
1
page
2
22, 28,
55
3
166
4
17
5
58
53
6
53
7
8
9
10
17
2.1 Peripheral devices