6. PROTECTIVE FUNCTIONS
6.5 Causes and corrective actions
E.CPU
E. 5
E. 6
E. 7
CPU fault
The inverter trips if the communication fault of the built-in CPU occurs.
Check for devices producing excess electrical noises around the converter unit.
• Take measures against noises if there are devices producing excess electrical noises around the converter
unit.
• Contact your sales representative.
E.CTE
Operation panel power supply short circuit/RS-485 terminals power supply short circuit
• When the power supply for the operation panel (PU connector) is shorted, the power output is shutoff and the
inverter output is shut off. At this time, the use of the operation panel and the RS-485 communication via the
PU connector are disabled.
To reset, enter the RES signal from the terminal, reset through communication via the RS-485 terminals, or
switch power OFF then ON again.
• When the power supply for the RS-485 terminals are short circuited, this function shuts off the power output.
At this time, communication from the RS-485 terminals cannot be made.
To reset, use
on the operation panel, enter the RES signal, or switch power OFF then ON again.
• Check that the PU connector cable is not shorted.
• Check that the RS-485 terminals are connected correctly.
• Check the operation panel and the cable.
• Check the connection of the RS-485 terminals.
E.P24
24 VDC power fault
• When the 24 VDC power output from the PC terminal is shorted, this function shuts off the power output.
At this time, all external contact inputs switch OFF. The inverter cannot be reset by entering the RES signal.
To reset it, use the operation panel, or switch power OFF, then ON again.
• Check for a short circuit in the PC terminal output.
• Check that the 24 V external power supply voltage is correct.
• Repair the short-circuited portion.
• Supply the power at 24 V. (If the power with insufficient voltage is supplied to the 24 V input circuit for a long
time, the inverter internal circuit may heats up. Although it will not damage the inverter, supply power at the
correct voltage.)
E.IOH
Inrush current limit circuit fault
The inverter output is shut off when the resistor of the inrush current limit circuit is overheated. The inrush current
limit circuit is faulty.
• Check that frequent power ON/OFF is not repeated.
• Check if the input side fuse (5A) in the power supply circuit of the inrush current limit circuit contactor is blown.
• Check that the power supply circuit of inrush current limit circuit contactor is not damaged.
Configure a circuit where frequent power ON/OFF is not repeated.
If the problem still persists after taking the above measure, contact your sales representative.
E.SER
Communication fault (inverter)
The inverter output is shut off when communication error occurs consecutively for the permissible number of
retries or more when Pr.335 RS-485 communication retry count ≠ "9999" during RS-485 communication
through the RS-485 terminals. The inverter output is also shut off if communication is broken for the period of
time set in Pr.336 RS-485 communication check time interval.
Check the RS-485 terminal wiring.
Perform wiring of the RS-485 terminals properly.