8.2 Common Specifications - Mitsubishi Electric FR-CC2-N Series Instruction Manual

Converter unit
Table of Contents

Advertisement

8.2
Common specifications
Input signal (3)
Operational function
Output signal
Open collector output (5)
Relay output (1)
Status
monitoring
*3
Operation panel
Fault
monitoring
Fault
Protective
function
Alarm,
Warning, Error
message
Surrounding air temperature
Surrounding air humidity
Storage temperature
Ambience
Altitude/vibration
*1
Applicable to conditions for a short time, for example, in transit.
*2
Not activated in the converter unit in the initial state.
*3
In the initial status, monitoring using the operation panel is not available. Remove the accessory cover and install the inverter operation panel.
(Refer to
168
8. SPECIFICATIONS

8.2 Common specifications

External thermal relay input, converter reset.
The signal to be input can be changed using Pr.178, Pr.187, or Pr.189 (Input terminal function
selection).
Thermal protection, DC injection brake, automatic restart after instantaneous power failure, retry
function, RS-485 communication, life diagnosis, maintenance timer, 24 V power supply input for
control circuit
Inverter operation enable (NO contact), Instantaneous power failure/undervoltage, Inverter reset, Fan
fault output, Fault
The signal to be output can be changed using Pr.190 to Pr.195 (Output terminal function
selection).
Converter output voltage, input current, electric thermal relay function load factor
The item for monitoring can be changed using Pr.774 to Pr.776 Operation panel monitor selection
1 to 3.
When a protective function is activated, a fault indication is displayed and the converter output
voltage, input current, electronic thermal relay function load factor, cumulative energization time, date
(year, month, day) and time at the occurrence of the fault are stored. Each fault is recorded and the
last 8 records can be displayed.
Overvoltage trip, Converter overload trip (electronic thermal relay function), Heat sink overheat,
Instantaneous power failure, Undervoltage, Input phase loss
*2
disconnection
Parameter storage device fault (main circuit board), CPU fault, 24 VDC power fault, Inrush current
limit circuit fault, Communication fault (inverter), Option fault, Operation panel power supply short
circuit/RS-485 terminals power supply short circuit, Internal circuit fault
Fan alarm, Electronic thermal relay function pre-alarm, Maintenance signal output
*2
lock
, Password locked
operation
-10°C to +40°C (non-freezing)
95% RH or less (non-condensing)
*1
-20°C to +65°C
Indoors (free from corrosive gas, flammable gas, oil mist, dust and dirt)
4000 m or less (For installation at an altitude above 1000 m, consider a 3% reduction in the rated
current per 500 m increase in altitude.) Frequency range 10 to 57 Hz: maximum amplitude 0.075 mm.
Frequency range 57 to 150 Hz: maximum acceleration speed 1G.
page
19.)
*2
, Retry count excess
, Parameter storage device fault (control circuit board),
*2
, Parameter write error, Copy operation error, 24 V external power supply
*2
, External thermal relay operation, PU
*2
, Operation panel