Commissioning (Basic Settings); Type Of Seating: Set - AUMA SAEx Series Operation Instructions Manual

Multi-turn actuators, control unit: electronic (mwg) with actuator controls, acexc 01.2 non-intrusive
Hide thumbs Also See for SAEx Series:
Table of Contents

Advertisement

SAEx 07.2
SAEx 16.2 / SAREx 07.2
ACExC 01.2 Non-Intrusive Profinet
9.

Commissioning (basic settings)

9.1.

Type of seating: set

Limit
Torque
Select main menu
Select parameter
CLOSE or OPEN
SAREx 16.2 Control unit: electronic (MWG)
1.
Set selector switch to position 0 (OFF).
Information: The selector switch is not a mains switch. When positioned to 0
(OFF), the actuator cannot be operated. The controls' power supply is
maintained.
2.
Switch on the power supply.
Information: Observe heat-up time for ambient temperatures below 30 °C.
3.
Perform basic settings.
Valve damage due to incorrect setting!
The type of seating setting (limit or torque seating) must match the selection for
the valve.
Only change the setting with prior consent of the valve manufacturer.
Customer settings M0041
Type of seating M0012
End position CLOSED M0086
End position OPEN M0087
Default value: Limit
Setting values:
Seating in end positions via limit switching.
Seating in end positions via torque switching.
1.
Set selector switch to position 0 (OFF).
2.
Press push button C Setup and hold it down for approx. 3 seconds.
Display goes to main menu and indicates: ▶ Display
3.
Select parameter either:
click via the menu
via direct display: Press
Display indicates: End position CLOSED
4.
Use
Up ▲ Down ▼ to select:
▶ End position CLOSED
▶ End position OPEN
The black triangle ▶ indicates the current selection.
5.
Press
Ok.
Display indicates the current setting: Limit or Torque
The bottom row of the display indicates either:
-
Edit → continue with step 6
-
Save → continue with step 10
Commissioning (basic settings)
to parameter, or
and enter ID M0086 or M0087
57