Commissioning (basic settings)
9.4.2.
Direction of rotation at hollow shaft/stem: check
Check direction of rota-
tion
9.4.3.
Limit switching: check
64
SAEx 07.2
SAEx 16.2 / SAREx 07.2
Figure 65: Direction of rotation of the hollow shaft/stem for operation in direction
CLOSE ("clockwise closing" version)
[1]
Threaded plug
[2]
Seal
[3]
Hollow shaft
[4]
Protective cap for stem protection tube
[5]
Stem
[6]
Stem protection tube
Valve damage due to incorrect direction of rotation!
If the direction of rotation is wrong, switch off immediately (press STOP).
Eliminate cause, i.e. correct phase sequence for cable set wall bracket.
Repeat test run.
1.
Move actuator manually to intermediate position or to sufficient distance from
end position.
2.
Depending on the version: Unscrew threaded plug [1] with seal [2], protective
cap [4] or stem protection tube [6].
3.
Switch on actuator in direction CLOSE and observe direction of rotation at hollow
shaft [3] or stem [5]:
The direction of rotation is correct if the actuator moves in direction CLOSE
and the hollow shaft in clockwise direction, or the stem moves downward.
4.
Correctly fit/screw on threaded plug [1] with seal [2], protective cap [4] for stem
protection tube [6], fasten thread.
1.
Set selector switch to position Local control (LOCAL).