External Earth Connection - AUMA SAEx Series Operation Instructions Manual

Multi-turn actuators, control unit: electronic (mwg) with actuator controls, acexc 01.2 non-intrusive
Hide thumbs Also See for SAEx Series:
Table of Contents

Advertisement

Electrical connection
5.3.

External earth connection

Application
36
SAEx 07.2
SAEx 16.2 / SAREx 07.2
Figure 27: Earth connection for multi-turn actuator
Figure 28: Earth connection for wall bracket
External earth connection (U-bracket) for connection to equipotential compensation.
Table 21:
Terminal cross sections and earth connection tightening torques
Conductor type
Solid wire and stranded
Fine stranded
For fine stranded (flexible) wires, connection is made via cable lugs/ring terminals. When connecting
two individual wires with a U-bracket, cross sections have to be identical.
SAREx 16.2 Control unit: electronic (MWG)
ACExC 01.2 Non-Intrusive Profinet
Terminal cross sections
2.5 mm² to 6 mm²
1.5 mm² to 4 mm²
Tightening torques
3
4 Nm
3
4 Nm