Hsp5 Operator With Screw Terminal (00F5060-9001); Hsp5 Operator With Rj45 Socket (00F5060-9002) - KEB combicontrol PCC C5 Instruction Manual

Table of Contents

Advertisement

COMBICONTROL

2.2.3 HSP5 Operator with screw terminal (00F5060-9001)

X6E Name
1
TXD-
2
TXD+
3
RXD-
4
RXD+
5
EnTXD- Handshake transmission signal-
6
EnTXD+ Handshake transmission signal+
7
EnRxD- Handshake receive signal-
8
EnRxD+ Handshake receive signal+
9
GND
10 VCC
-
Shielding Shielding (see figure)

2.2.4 HSP5 Operator with RJ45 socket (00F5060-9002)

RJ45
Name
1
RXD+
2
RXD-
3
GND
4
TXD+
5
TXD-
6
GND
7
EnRxD+ Handshake receive signal+
8
EnRxD- Handshake receive signal-
-
Shielding Shielding
The connection to the control is realized with a commercial CAT5 Patch cable for this ope-
rator.
X6E
Description
Transmission signal-
Transmission signal+
Receive signal-
Receive signal+
Reference potential
+24 V voltage output
Description
Receive signal+
Receive signal-
Reference potential
Transmission signal+
Transmission signal-
Reference potential
No cables may be connected
to terminal VCC. High voltage
can destroy the interface in the
control.