1.3 DELIVERY - TRANSPORT - STORAGE

1.3.1 INTRODUCTION

This chapter contains all the necessary information for the correct unpacking, positioning, cabling and installation
of the UPS.
The UPS and accessories are delivered on a specifically designed pallet that is easy to move with a forklift or a
pallet jack. Keep the UPS always in upright position and do not drop the equipment. Do not either stack the pallets
because of high-energy batteries involved and the heavy weight
!
NOTE!

1.3.2 RECEIPT OF THE UPS AND VISUAL INSPECTION

Upon receiving the UPS, carefully examine the packing container and the UPS for any sign of physical damage.
The outside 'Tip&Tel' ( "FRAGILE" and "ARROW") indicator should be intact if the equipment has been transported
in the upright position. In case of rupture or suspect inform immediately:
The carrier and
The manufacturer
Ensure that the received UPS corresponds to the material indicated in the delivery note.
The packing container of the UPS protects it from mechanical and environmental damage. To increase its
protection the UPS is wrapped with a plastic sheet.
!
NOTE!
IF THE UPS IS NOT IMMEDIATELY INSTALLED THE FOLLOWING GUIDELINES
MUST BE FOLLOWED:
TRANSPORT:
UPS CABINETS AND/OR BATTERY CABINET CAN FALL OVER. USE THE
SHIPPING BRACKETS ON THE REAR AND FRONT TO SECURE THE
CABINETS. DO NOT TILT THEM MORE THAN 10° FROM VERTICAL,
OTHERWISE CABINETS MAY TIP OVER.
POTENTIAL DANGERS:
TILTING THE CABINET MIGHT DAMAGE THE SYSTEM AND
THEREFORE SHOULD NO LONGER BE CONNECTED TO THE MAINS.
WEIGHT OF THE UPS SYSTEM COULD CAUSE SERIOUS INJURIES TO
PERSONS OR ANYTHING IN THE SURROUNDING AREA.
STORAGE:
THE UPS SHOULD BE STORED IN THE ORIGINAL PACKING AND
SHIPPING CARTON
THE RECOMMENDED STORING TEMPERATURE FOR THE UPS
SYSTEM AND BATTERIES IS BETWEEN +20°C AND +25°C.¨
THE UPS SYSTEM AND THE BATTERIE SETS MUST BE PROTECTED
FROM HUMIDITY < 95% (NON-CONDENSING).
VISIBLE TRANSPORT DAMAGES MUST BE CLAIMED TO THE CARRIER
IMMEDIATELY AFTER RECEIPT !!
OTHER CLAIM FOR SHIPPING DAMAGE MUST BE FILED IMMEDIATELY TOO
AND THE CARRIER MUST BE INFORMED WITHIN 7 DAYS OF RECEIPT OF THE
EQUIPMENT. THE PACKING MATERIALS SHOULD BE STORED FOR FURTHER
INVESTIGATION.