2.1.3 CONNECTION DIAGRAM POWERSCALE

Cable Sections and Fuse Ratings recommended. Alternatively, local standards to be respected
Block Diagram
SINGLE INPUT FEED
Fuse A
Cable A
FA1
Cable E
Rectifier
F1/FA3
Fuse E
Inverter
Static Switch
IA2
Frame
Figure 3: Block Diagram POWERSCALE from 10-50 kVA
SINGLE INPUT FEED – Cable sections and fuse ratings recommended according to IEC 60950-1
Fuse A
UPS
Power
1L1, 1L2, 1L3
Cabinet
[kVA]
[quantity x A]
10
A, B
3 x 20
15
A, B
3 x 32
20
A, B
3 x 40
25
B, C
30
C
3 x 63
40
C
3 x 80
50
DUAL INPUT FEED – Cable sections and fuse ratings recommended according to IEC 60950-1
Fuse B
UPS
Power
1L1, 1L2, 1L3
Cabinet
[kVA]
[quantity x A]
10
A, B
3 x 20
15
A, B
3 x 32
20
A, B
3 x 40
25
B, C
30
C
3 x 63
40
C
3 x 80
50
MAINS (3x380V/220V,
3x400/230V,3x415/240V)
FA2
IA1
Mainten. Bypass
Cable D
Load
Cable A
1L1, 1L2, 1L3, N, PE
2
[quantity x mm
]
5 x 2.5
5 x 4
5 x 6
5 x 10
(1L1, 1L2, 1L3, N): 4 x 25
(PE): 1 x 16
Cable B
1L1, 1L2, 1L3, N, PE
2L1, 2L2, 2L3
2
[quantity x mm
]
[quantity x A]
5 x 2.5
5 x 4
5 x 6
5 x 10
(1L1, 1L2, 1L3, N):
4 x 25
1 x 16
(PE):
04-3004_S2_OPM_ABB_POWERSCALE_10-50kVA_EN_150113.doc
Printed in Switzerland – Modifications reserved
DUAL INPUT FEED
Fuse B
Cable B
Cable E
Rectifier
F1/FA3
Fuse E
Inverter
Static Switch
Frame
Cable D
3L1, 3L2, 3L3, N, PE
[quantity x mm
5 x 2.5
5 x 4
5 x 6
5 x 10
(3L1, 3L2, 3L3, N): 4 x 25
(PE): 1 x 16
Fuse C
Cable C
2L1, 2L2, 2L3, N, PE
2
[quantity x mm
]
3 x 20
5 x 2.5
3 x 32
5 x 4
3 x 40
5 x 6
3 x 63
4 x 10
(2L1, 2L2, 2L3, N):
4 x 25
3 x 80
1 x 16
(PE):
Fuse C
MAINS (3x380V/220V,
3x400/230V,3x415/240V)
Cable C
FA2
FA1
IA1
IA2
Mainten. Bypass
Cable D
Load
Fuse E
+, N, -, PE
2
]
[quantity x A]
3 x 32
3 x 50
3 x 80
3 x 100
Cable D
Fuse E
3L1, 3L2, 3L3, N, PE
+, N, -, PE
2
[quantity x mm
]
[quantity x A]
5 x 2.5
3 x 32
5 x 4
5 x 6
3 x 50
5 x 10
3 x 80
(3L1, 3L2, 3L3, N):
4 x 25
3 x 100
1 x 16
(PE):
Section-2
Cable E
+, N, -, PE
2
[quantity x mm
]
4 x 4
4 x 10
4 x 16
(+, N, -): 3 x 25
(PE): 1 x 16
Cable E
+, N, -, PE
2
[quantity x mm
]
4 x 4
4 x 10
4 x 16
(+, N, -):
3 x 25
1 x 16
(PE):