ABB PowerValue RT G2 User Manual

ABB PowerValue RT G2 User Manual

Ups 5-10 kva ul
Table of Contents

Advertisement

Quick Links

U S E R M A N UA L
UPS PowerValue RT G2
5-10 KVA UL
© Copyright 2022 ABB, All rights reserved.

Advertisement

Table of Contents
loading

Summary of Contents for ABB PowerValue RT G2

  • Page 1 — U S E R M A N UA L UPS PowerValue RT G2 5-10 KVA UL © Copyright 2022 ABB, All rights reserved.
  • Page 2 A B B U P S P R O D U C T S A N D S O L U T I O N S — About this manual — Document information File name 4NWD005649_OPM_ABB_PVA_5-10kVA-RT-UL_EN_REV-A UPS model PowerValue 11 RT G2 5-10kVA UL Date of issue 23.08.2022 Issued by...
  • Page 3: Table Of Contents

    — Contents Important safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 1 .1 Operator precautions .
  • Page 4 A B B U P S P R O D U C T S A N D S O L U T I O N S Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 6 .1 RS-232 port .
  • Page 5: Important Safety Instructions

    CABINET: DANGER OF ELECTRICAL SHOCK. DANGER accidental load loss. HIGH FAULT CURRENTS (LEAKAGE CURRENTS). BEFORE CONNECTING THE ABB DOES NOT TAKE ANY RESPONSIBILITY FOR MAINS ENSURE THAT THE UPS IS EARTHED! DAMAGES CAUSED THROUGH INCORRECT USE DANGER DISPLAY A WARNING LABEL ON ALL OF THE UPS SYSTEM .
  • Page 6: Declaration Of Safety Conformity And Ul Marking

    A B B U P S P R O D U C T S A N D S O L U T I O N S — 1 .3 Declaration of safety conformity and UL marking The UPS PowerValue RT G2 5-10 kVA UL is These products also meet the following designed, manufactured and commercialized in...
  • Page 7: Maintenance

    • MAKE USE OF PROPER PPE (PERSONAL years at 25 °C ambient temperature). Contact PROTECTION EQUIPMENT) AS PER LOCAL POLICIES AND RULES your local ABB or an agent authorized by ABB for - WEAR FLAME/ARC RESISTANT replacements. WHOLE BODY CLOTHING •...
  • Page 8: Ups Disposal And Recycling

    A B B U P S P R O D U C T S A N D S O L U T I O N S — 2 .1 UPS disposal and recycling 2 .1 .1 For professional users in the European Union 2 .1 .2 For disposal in countries outside of the European Union THE CROSSED –...
  • Page 9: General Characteristics

    3 G E N E R A L C H A R A C T E R I S T I C S — 3 General characteristics — 3 .1 UPS front panel UPS rear panel 3 .1 .1 UPS front panel —...
  • Page 10: Ups Rear Panel

    A B B U P S P R O D U C T S A N D S O L U T I O N S — 3 .1 .2 UPS rear panel 3.1.2-1: UPS rear panel — 3.1.2-1 DIAGRAM 1: 5KRT/6KRT/8KRT/10KRT REAR PANEL Item AC Output terminal AC Input terminal...
  • Page 11: Bat Rear Panel

    3 G E N E R A L C H A R A C T E R I S T I C S — 3 .2 BAT rear panel — 3 .2 .1 BAT rear panel 3.2.1-1: BAT rear panel DC BREAKER 63A/440V BATTERY...
  • Page 12: Installation

    Be sure to deliver the spent battery to a and check the following items are included: recycling facility or ship it to your dealer in the • 1 x PowerValue RT G2 UPS replacement battery packing material. • 1 X USB flash drive •...
  • Page 13: Site Planning And Positioning

    I N S TA L L AT I O N — 4 .2 Site planning and positioning • MAKE SURE THE MAINS SUPPLY AND THE TOTAL LOAD DEMAND ARE WITHIN UPS SPECIFICATIONS WARNING 4 .2 .1 Planning before the installation To ensure a long service life, install the unit in a position where any danger to the UPS is minimized: •...
  • Page 14: Installation

    — Step 3 . Adjust the distance of rail sliders by 4.3.1-1: PowerValue RT G2 5-10KAV UL can be mounted in Step 1 pulling the other end. It should be the same depth a rack or installed in a standalone configuration.
  • Page 15: Tower Installation

    I N S TA L L AT I O N 4 .3 .3 Tower Installation — 4.3.3-1-1: The UPS module is shipped with two sets of feet Step 1 and 2 short extensions that can be used to tower — 4.3.3-1-2: install the UPS module in 3U.
  • Page 16: Electrical Installation

    A B B U P S P R O D U C T S A N D S O L U T I O N S — 4 .4 Electrical installation — 4.4.1-1: • MAKE SURE THE MAINS SUPPLY AND THE TOTAL LOAD DEMAND ARE WITHIN UPS SPECIFICATIONS. Wiring Terminal Blocks •...
  • Page 17: Operation

    5 O P E R AT I O N — 5 Operation This chapter describes how the UPS is operated through the LCD. The user can: • Operate the LCD • Start up and shut down the UPS (excluding the commissioning start up) •...
  • Page 18: Led Indicators

    A B B U P S P R O D U C T S A N D S O L U T I O N S 5 .1 .2 LED Indicators There are 4 LEDs on front panel to show the UPS 5 .1 .4 Table Audible alarm working status: UPS status...
  • Page 19: Operating Mode

    5 O P E R AT I O N — 5 .2 Operating mode The following table describes the UPS status information: — Table : Symbols in operating mode Status LCD Screen Description Power On Mode M I P 1 : 1 2 0 . 6 V / 4 9 . 9 H z I P 2 : 1 2 0 .
  • Page 20: Ups Start-Up And Shutdown

    A B B U P S P R O D U C T S A N D S O L U T I O N S — 5 .3 UPS start-up and shutdown 5 .3 .1 UPS start-up To start up the UPS with mains supply: 1.
  • Page 21 5 O P E R AT I O N 5 .3 .2 UPS shutdown To shut down the UPS with mains supply: 1. The LCD is on home page, press the “OFF/ESC” button, LCD will show a prompt page of “Turn Off”; Move the arrow to “Yes”...
  • Page 22: Parallel Ups Operation

    A B B U P S P R O D U C T S A N D S O L U T I O N S — 5 .4 Parallel UPS Operation 5 .4 .1 Parallel machine installation — 5.4.1-1: Up to 4 units can be paralleled.
  • Page 23: Install A New Parallel Ups System

    0.5V. If (Figure 5.4.2-5). the difference is greater than 0.5V, please contact your local ABB office or an ABB INTELLIGENT SLOT INPUT BREAKER~ IN OUT authorized agent.
  • Page 24: A Single Ups From A Parallel Machine System

    A B B U P S P R O D U C T S A N D S O L U T I O N S 5 .4 .3 A single UPS from a parallel machine system: 5 .4 .4 Re-enter the unit into the parallel system —...
  • Page 25: Lcd Operation On Ups Module

    5 O P E R AT I O N — 5 .5 LCD Operation on UPS Module 5 .5 .1 . LCD Structure The entire LCD structure is demonstrated as diagram below. Press button “Enter” Press button “Esc” Press button “Enter” Press button “Esc”...
  • Page 26: Operation Menu

    A B B U P S P R O D U C T S A N D S O L U T I O N S 5 .5 .2 Operation menu 5.5.2-1. Main menu 5.5.2-2. Control Turn on Turn off Bat Test MENU Main...
  • Page 27 5 O P E R AT I O N Turn On/Turn Off This item is for turning on/off the UPS. a) On Bypass mode or Standby mode, it will display “Turn On” in control menu. If it is selected and confirmed, the UPS will transfer to line mode, CVCF mode, ECO mode, or battery mode according to the setting and input status.
  • Page 28 A B B U P S P R O D U C T S A N D S O L U T I O N S Bat Test Mode M I P 1 : 1 2 0 . 0 V / 4 9 . 9 H z I P 2 : 1 2 0 .
  • Page 29 5 O P E R AT I O N SR On / SR Off a) On Line/Battery/Battery Test/CVCF/ECO mode, it will display “SR On” in control menu. If it is selected and confirmed, shutdown and restore time can be setting. Please refer to setting range table for shutdown and restore time.
  • Page 30 A B B U P S P R O D U C T S A N D S O L U T I O N S 5.5.2-3. Measurement Measurement displays the measurement value of the parameters such as voltage / current / frequency / power / capacity / time etc.
  • Page 31 5 O P E R AT I O N 5.5.2-4. Setting This page is used to configure the parameter settings. There are submenus under the Setting, including Bypass, ECO, Output, SystemTime, Others and Battery, as shown below. Bypass Output Select“Yes” Main Menu Setting...
  • Page 32 A B B U P S P R O D U C T S A N D S O L U T I O N S 02: ECO setting (only available or effective on bypass mode, standby mode, Line mode and ECO mode) Interface Description 1.Status...
  • Page 33 5 O P E R AT I O N 05: Others setting Interface Description 1. Hot standby (only available or effective on bypass mode and standby mode): Enable: Hot standby function is enabled. It means that the current UPS is set to be host of hot standby system, and it will automatically restart after AC recovery even without O t h e r s : battery connected.
  • Page 34 A B B U P S P R O D U C T S A N D S O L U T I O N S 06: Battery Interface Description 1.Dischg Protect: Enable or disable battery discharge protection. Enable: Battery discharge protection function is enabled. When UPS have been continuously working in “battery/battery test mode”, the UPS will automatically shut down when the backup time set next is achieved.
  • Page 35 5 O P E R AT I O N 5.5.2-5. Information In Information page, you can check the serial number, firmware versions, system configuration and settings of the UPS. There are submenus under the Information, including Identification, System and Battery, as shown below.
  • Page 36 A B B U P S P R O D U C T S A N D S O L U T I O N S 5.5.2-6. Events In Event pages, you can check the current events, history events and reset events. Current Events Events Main...
  • Page 37: Communication

    6 C O M M U N I C AT I O N — 6 Communication A USB and an RS-232 port are available to enable If there is a power failure and a predicted communication between the UPS and a remote shutdown of the UPS due to low battery computer/ station.
  • Page 38: Usb Port

    A B B U P S P R O D U C T S A N D S O L U T I O N S — 6 .2 USB port The UPS can communicate with USB-compliant computers that run power management software.
  • Page 39: Output Dry Contact Port

    6 C O M M U N I C AT I O N — 6 .4 Output Dry Contact Port 6 .4 .1 Dry IN 6 .4 .2 Dry OUT — 6.4.1-1: Dry in allows a remote action to switch on/ The dry out port is normally open.
  • Page 40: Troubleshooting

    A B B U P S P R O D U C T S A N D S O L U T I O N S — 7 Troubleshooting — 7 .1 Warning status When Fault LED flashes and the buzzer beeps once every second, it means that there are some problems with UPS.
  • Page 41: Trouble Shooting Table

    7 T R O U B L E S H O OT I N G — 7 .3 Trouble shooting table Most of the fault and warnings need to be released by authorized service personnel. Few of them can be solved by users themselves. LCD Message Explanation Solution...
  • Page 42 A B B U P S P R O D U C T S A N D S O L U T I O N S LCD Message Explanation Solution Fault 23:Op STS Open Output relay or STS is open. Contact service personnel.
  • Page 43 7 T R O U B L E S H O OT I N G LCD Message Explanation Solution Warning 06:LineVoltError As stated. Check if the input wiring is correct or contact service personnel Warning 07:LinePhaseFail As stated. Contact service personnel Warning 08:OverCharge Battery voltage is too high.
  • Page 44 A B B U P S P R O D U C T S A N D S O L U T I O N S LCD Message Explanation Solution Warning 19:LineDiff Each module gets different line Contact service personnel. voltage when they are in parallel.
  • Page 45: Cyber Security Legal Disclaimer

    ABB Ltd and its affiliates are not liable for damages and/or losses related to such security breaches any unauthorized access, interference, intrusion, leakage and/or theft of data or information.
  • Page 46: Ups Technical Specification

    A B B U P S P R O D U C T S A N D S O L U T I O N S — 9 UPS Technical Specification — GENERAL DATA 5 kVA 6 kVA 8 kVA 10 kVA Apparent power 5 kVA...
  • Page 47 U P S T E C H N I C A L S P E C I F I C AT I O N — INPUT CHARACTERISTICS 5 kVA 6 kVA 8 kVA 10 kVA Acceptance voltage 88-155VAC (L-N)/ 88-155VAC (L-N)/ 88-155VAC (L-N)/ 88-155VAC (L-N)/ (steady-state, r.m.s)
  • Page 48 A B B U P S P R O D U C T S A N D S O L U T I O N S — OUTPUT CHARACTERISTICS 5 kVA 6 kVA 8 kVA 10 kVA Rated power 5000 W 6000W 8000 W 9000 W...
  • Page 49 U P S T E C H N I C A L S P E C I F I C AT I O N — BATTERY CHARACTERISTICS 5 kVA 6 kVA 8 kVA 10kVA VRLA, VRLA, VRLA, VRLA, Technology vented lead-acid vented lead-acid vented lead-acid vented lead-acid...
  • Page 50 — www.abb.com/ups ups.sales@ch.abb.com © Copyright 2022 ABB. All rights reserved. Specifications subject to change without notice.

Table of Contents