10.8.4 CUSTOMER INTERFACES:
10.8.5 CUSTOMER INPUTS DRY PORTs:
Connection of Remote Shut down facilities, Generator Operation, Customers specials
(see UM Section 9 / OPTIONS)

10.8.6 CUSTOMER OUTPUTS DRY PORTs : Terminal blocks X1 (optional relay slot card)

Provision of signals for the automatic and orderly shutdown of servers, AS400 or Automation building systems
All voltage free contacts are rated 60 VAC max. and 500 mA max.:
All the interfaces are connected to Phoenix Spring terminals with wires : 0.5 mm
Block Terminal Contact
GND
X1 / 10
X1
X1 / 9
IN
GND
X1 / 8
X1 / 7
IN
GND
X1 / 6
X1 / 5
IN
GND
X1 / 4
X1 / 3
IN
GND
X1 / 2
X1 / 1
IN
X1 / 15
C
X1
X1 / 14
NC
X1 / 13
NO
C
X1 / 12
X1 / 11
NC
X1 / 10
NO
X1 / 9
C
X1 / 8
NC
X1 / 7
NO
C
X1 / 6
X1 / 5
NC
X1 / 4
NO
X1 / 3
C
X1 / 2
NC
X1 /1
NO
+ USB
Phoenix Spring Terminals (X1) Connection
Terminals X1 Standard
Terminal block X1
Signal
On Display
GND
+12Vdc
GND
+12Vdc
GND
+3.3Vdc
GND
+12Vdc
GND
+12Vdc
COMMON_ALARM
ALARM
LOAD_ON_MAINS
Message
BATT_LOW
ALARM
LOAD_ON_INV
Message
MAINS_OK
ALARM
04-3004_S10_TDS_ABB_POWERSCALE_10-50 kVA_EN_150113.doc
Printed in Switzerland – Modifications reserved
Function
12 Vdc source
(Max 200mA load)
Remote Shut down
(Do not remove the factory mounted bridge until an external remote shut down is connected)
Temperature Battery
(If connected, the battery charger current is batt. temperature dependent)
Customer IN 1
(Function on request, to be defined)
GEN_OPERATION
(NC = Generator ON)
Common
NO Alarm Condition
Common Alarm (System)
Common
(Load on Inverter)
Load on bypass (Mains)
Common
Battery OK
Battery Low
Common
(Load on Mains bypass)
Load on Inverter
Common
Mains Failure
Mains Present
2
Page 11/20 ABB
Section-10