2.3

BATTERY CONNECTIONS

2.3.1 BATTERY BANKS CABINETS A, B, C AND EXTERNAL BATTERY

PowerScale has additional battery enclosure. In the drawing below the Battery enclosures are shown.
NOTE: Within the cabinets A & B in only 7/9Ah batteries are allowed (20-48 blocks), in Cabinet C also 28Ah
batteries are allowed
Cabinet A (max. 48 blocks)
Battery bank
NOTE: Set-up the correct number of battery blocks on Control Panel (Menu: Service-Set-Up).
Cabinet C (max 144 blocks, 3x48 7/9Ah or max. 48 blocks 28Ah)
PS-Cabinet-C-
PS-Cabinet-C-
48x28Ah
96x9Ah
Battery bank
PS-Cabinet-C-
144x9Ah
04-3004_S2_OPM_ABB_POWERSCALE_10-50kVA_EN_150113.doc
Printed in Switzerland – Modifications reserved
Cabinet B (max.96 blocks) (2x48 blocks)
Battery bank
Section-2
Battery bank
PS-Cabinet-C-
Standard