2.3.1.2 Connection of External Battery for PowerScale

It is normally recommended for redundant systems to provide each UPS with its own separate battery. In this
way the redundancy is extended also to the batteries. In the Figure 4 the drawing shows how to connect the
batteries in the external battery cabinet and the PowerScale frame.
!
NOTE!
To ensure protection of the personnel during the installation of the UPS make sure that the connections
are performed under the following conditions:
!
No mains voltage is present in the UPS
All the loads are disconnected
The UPS and the external battery are voltage-free
To verify the complete shut down of the PowerScale perform following steps:
1) Make sure that the fuses feeding the UPS in the input Distribution Board are all open and no power is
fed to the UPS.
2) Make sure the "MAINTENANCE BYPASS"(IA1) is open (position "OFF")
3) Make sure the battery fuses in the external battery cabinet or racks and on the UPS are open.
4) Connect Earth (PE) between the UPS and external battery cabinet.
5) Connect the corresponding + , N, - terminals between UPS and external battery cabinet according to
drawing

2.3.1.3 Terminals for External Battery connection

External Battery for separate Batteries per UPS
+ N -
Figure. 4 Connection of external separate batteries
ALL THE OPERATIONS IN THIS MANUAL MUST BE PERFORMED BY CERTIFIED
ELECTRICIANS OR BY QUALIFIED INTERNAL PERSONNEL.
DO NOT OPERATE IN CASE OF PRESENCE OF WATER OR MOISTURE.
BY OPENING OR REMOVING THE UPS-COVERS YOU RUN RISK OF EXPOSURE
TO DANGEROUS VOLTAGES.
04-3004_S2_OPM_ABB_POWERSCALE_10-50kVA_EN_150113.doc
Printed in Switzerland – Modifications reserved
Section-2
Page 13/15 ABB