Environmental Characteristics; Standards; Communication - ABB PowerScale CABINET A User Manual

Table of Contents

Advertisement

10.6 ENVIRONMENTAL CHARACTERISTICS

UPS range
Audible Noise with
100% / 50% Load
Operation temperature
Ambient Temperature
for Batteries
(recommended)
Storage Temperature
Battery Storage Time at
Ambient Temperature
Max. altitude (above sea
level)
De-rating factor for use
at altitudes above
1000m sea level
according
( IEC 62040-3)
Relative Air-humidity
Accessibility
Positioning
Input and Output Power
Cabling
Efficiency AC-AC
(at cosφ1.0)
(
depending on power rating)
Eco-Mode efficiency at
100% load

10.7 STANDARDS

Safety
Electromagnetic Compatibility
EMC Classification for
Emission Class
Immunity Class
Performance
Product certification
Degree of protection

10.8 COMMUNICATION

STANDARD ITEMS
10kVA
15kVA
dBA
60/53
60/53
°C
°C
°C
m
Meter above sea level (m / ft)
1500 / 4850
2000 / 6600
2500 / 8250
3000 / 9900
Rear access
Rear side bottom
Load
:
100 %
%
95.5%
%
10kVA
C2
04-3004_S10_TDS_ABB_POWERSCALE_10-50 kVA_EN_150113.doc
Printed in Switzerland – Modifications reserved
20kVA
25kVA
58/50
58/50
0 – 40
20 – 25
-25 – +70
Max. 6 months
1000m (3300ft) without de-rating
Max. 95% (non-condensing)
Min. 20 cm rear space (required for fan)
75 %
50%
95.5%
95%
98 %
IEC/EN 62040-1, IEC/EN 60950-1
IEC/EN 62040-2, IEC/EN61000-3-2,
IEC/EN61000-6-2
15-50kVA
C3
IEC/EN62040-3
CE
IP 20
30kVA
40kVA
58/50
58/50
De-Rating Factor for Power
0.95
0.91
0.86
0.82
Front access
Front side bottom
25%
94.5%
C3
Page 9/20 ABB
Section-10
50kVA
65/51

Advertisement

Table of Contents
loading

This manual is also suitable for:

Powerscale cabinet bPowerscale cabinet c