Preparation For The Input Cabling; Mains Supply And Earth Connection - ABB PowerScale CABINET A User Manual

Table of Contents

Advertisement

1.5.1 PREPARATION FOR THE INPUT CABLING

NOTE!
!
Mains voltage (INPUT VOLTS) and frequency (FREQUENCY) correspond to the values indicated on
the Nameplate of the UPS.
Earth connection is performed in accordance with the prescribed IEC Standards or with local
regulations;
UPS is connected to the mains through a Low Voltage (LV)-Distribution Board with a separate mains
line (protected with a circuit breaker or fuse) for the UPS.
Provide input fuses and cables according to
Standards or with the local regulations.
The input of the UPS must be fitted with circuit breakers or other kind of protection. The circuit breakers will be
connected between the mains supply and the UPS and will provide additional protection to the UPS in the event of
overloads and short circuits.
1.5.1.1

Mains Supply and Earth connection

To ensure protection of personnel during the installation of UPS make sure that the connections are performed
under the following conditions:
No mains voltage is present
All Loads are shut down and disconnected
The UPS System is shut down and voltage-free
The UPS System is fitted in its correct position
Maintenance Bypass IA1 is open and in position OFF;
Parallel Isolators IA2 is in position OFF
Remove Terminal cover of the UPS
1. Connect first the Earthing wire coming from the Low Voltage-Distribution Board to the terminal "PE".
2. Connect the input power cable coming from the Low Voltage-Distribution Board to the terminals of the
UPS showed in
3. Keep the phase rotation in clock-wise sense.
!
NOTE!
Under the connection terminal of the UPS there is a cable-fixing rail to ensure that the cables have been fastened
properly.
NOTE: The UPS is provided with facilities for both single feed (one common input cable for rectifier and bypass)
and dual feed (separate input cable for rectifier and bypass).
Before proceeding read the chapter
and insure before starting connecting the cable to the UPS that:
Section 2, chapter 2.1.3
Section 2, chapter 2.1.2.1
INPUT NEUTRAL IS REQUIRED TO OPERATE THE RECTIFIER.
04-3004_S1_OPM_ABB_POWERSCALE_10-50kVA_EN_150113.doc
Printed in Switzerland – Modifications reserved
ELECTRICAL INSTALLATION
or in accordance with the prescribed IEC
Section-1
(Section 1)
Page 16/20 ABB

Advertisement

Table of Contents
loading

This manual is also suitable for:

Powerscale cabinet bPowerscale cabinet c

Table of Contents