2.1.2.3 Cabinet C (40-50 kVA) terminal connections overview
Battery
(+ / N / - ) + PE
2
[quantity x mm
]
(+ / N / - ):
3 x 35
PE:
1 x 16
Input Rectifier
1L1, 1L2, 1L3 + N + PE
2L1, 2L2, 2L3 + N + PE
2
[quantity x mm
]
1L1, 1L2, 1L3 + N:
4 x 35
PE:
1 x 16
04-3004_S2_OPM_ABB_POWERSCALE_10-50kVA_EN_150113.doc
Printed in Switzerland – Modifications reserved
Input Bypass
3L1, 3L2, 3L3 + N + PE
2
[quantity x mm
]
2L1, 2L2, 2L3 + N:
3L1, 3L2, 3L3 + N:
4 x 35
PE:
1 x 16
Output load
Tightening Torque
2
[quantity x mm
]
4 x 35
PE:
1 x 16
Page 3/15 ABB
Section-2
[Nm]
2
35 mm
:
3.5
2
16 mm
:
1.5