• Connect the individual shields and the overall shield (if present) of
encoder cables to the separate shield grounding point (Fig. 6-33).
IMPORTANT! DO NOT connect the shields to the terminals of
the interface.
• Different-sized ground clamps are supplied.
(1) Exposed cable shielding
(2) Ground clamp (SK8)
(3) Ground clamp (SK14)
6.8.7

Routing cables in an EXU cabinet

This section applies to a stand-alone EXU.
6.8.7.1

Auxiliary power and control cables

1. Enter the cables through a free hole of the EMC plate.
2. On the length of cable that passes through the cable transit, prepare
the cable according to the following instructions:
• Cable entries with EMC plates: "6.8.4 Preparing cables for EMC
plates" on page 145
• Cable entries with cable glands: "6.8.3 Preparing cables for cable
glands" on page 145.
Note: Materials for cable fitting, EMC requirements and sealing are not
supplied for undrilled plates.
3BHS842007 E01 REV C
1
2
3
Figure 6-33 Shield grounding for encoder cable
ACS6080 USER MANUAL
06 ELECTRICAL INSTALLATION
4
5
(4) Ground clamp
(5) Encoder
150/238