A
Figure 6-35 Shield grounding point for encoder cable on NTAC pulse encoder (A)
and synchronous serial interface (B)
1) Terminals
1) Shield grounding point

6.8.7. Routing cables in an EXU cabinet

This section applies to a stand-alone EXU.

6.8.7.1. Auxiliary power and control cables

1. Enter the cables through a free hole of the EMC plate.
2. On the length of cable that passes through the cable transit, prepare the
cable according to the following instructions:
Cable entries with EMC plates: "6.8.4 Preparing cables for EMC plates"
on page 141
Cable entries with cable glands: "6.8.3 Preparing cables for cable glands"
on page 141.
NOTE – Materials for cable fitting, EMC requirements and sealing are not
supplied for undrilled plates.
PRODUCT
ACS6000
2
1
2
2
3
DOCUMENT KIND
User manual
B
2
2) Ground clamp
DOCUMENT ID.
3BHS212794 E01
ELECTRICAL INSTALLATION
1
REV.
LANG.
PAGE
N
en
147/266