5. Disconnect the water tubes (1) from the air-to-water heat exchanger,
unplug the cables (2) and remove the fastening screws.
(1) Water tube connections
(1) Fastening screw
6. Lift the heat exchanger out of the cabinet.
CAUTIONThe heat exchanger weighs approximately 16 kg and requires
a minimum overhead clearance of 85 cm.