Starting the drive locally

1. Set the control panel to local mode with the Loc/Rem key.
2. If the EMERGENCY-OFF RESET push button on the COU is flashing,
press the push button to cancel flashing.
Note: Each time the auxiliary voltage is switched off and on again, the
emergency-off safety relay of the drive is actuated and lets the
EMERGENCY-OFF RESET pushbutton flash. The EMERGENCY-OFF
RESET push button also flashes if the EMERGENCY-OFF push button
on the control compartment door, or any other EMERGENCY-OFF push
button linked to the drive, is pressed. If the EMERGENCY-OFF RESET
push button continuous flashing, verify that there is no emergency-off
command active. See "8.11.2 Stopping the drive with the emergency-
off function" on page 181
3. Check that no alarm or fault messages are displayed on the
control panel.
• When a fault message is displayed on the control panel, reset
the fault.
• If a fault cannot be reset, the responsible personnel must rectify it.
• (Drives with an ARU) When faults are present and the drive is ready,
the INU is "Ready to switch on".