Advertisement

5. Arrange the bunches according to size from thickest to the thinnest between the E
5. Arrange the bunches according to size from thickest to the thinnest between the EMI
conductive cushions.
conductive cushions.
6. If more than one cable go through a grommet, seal the grommet by applying Loctite
5221 (or equivalent adhesive sealant) inside the grommet.
6. If more than one cable go through a grommet, seal the grommet by applying Loct
5221 (catalogue number 25551) inside the grommet.

Routing the control cables inside the cabinet

Use the existing trunking in the cabinet wherever possible. Use sleeving if cables are laid
Routing the control cables inside the cabinet
against sharp edges. When running cables to or from a swing-out frame, leave enough
Use the existing trunking in the cabinet wherever possible. Use sleeving if cables are
slack at the hinge to allow the frame to open fully.
against sharp edges. When running cables to or from the swing-out frame, leave enou

Connecting control cabling

slack at the hinge to allow the frame to open fully.
Connect the conductors to the appropriate terminals. Refer to the wiring diagrams delivered
with the drive.
Connecting to the inverter control unit (A41)
With option +L504, the terminals of the inverter control unit are available on terminal block
Connect the conductors to the appropriate terminals (see page 127) of the control uni
X504.
terminal block X504 (option +L504).
Connect the inner twisted pair shields and all separate grounding wires to the grounding
Connect the inner twisted pair shields and all separate grounding wires to the groundi
clamps closest to the terminals.
clamps below the control unit.
The drawing below represents the grounding of the control cabling when connecting to a
The drawing below represents a drive with additional I/O terminal block (option +L504
terminal block inside the cabinet. The grounding is done in the same way when connecting
directly to a component such as the control unit.
Without the block, the grounding is made the same way.
Notes:
Do not ground the outer shield of the cable here since it is grounded at the lead-
through.
Keep any signal wire pairs twisted as close to the terminals as possible. Twisting
wire with its return wire reduces disturbances caused by inductive coupling.
Electrical installation
Electrical installation 105