Connecting The Detector Cables To The Arc Monitor Device - ABB ACS6080 User Manual

System drives
Hide thumbs Also See for ACS6080:
Table of Contents

Advertisement

6.4.2.1

Connecting the detector cables to the arc monitor device

To complete the optical fiber installation, the optical fibers must be
routed to the arc monitor device in the REB.
1. Pull all cables through the cable duct (3 in Fig. 6-8) at the top of
the cabinets.
Note: Cut-outs in the ducts provide entry into the cabinets.
(1) Cable tray for auxiliary power
supply cable
(2) Cable tray for control cables
2. Lay the cables into their designated trays and cable ducts as
illustrated in Fig. 6-8.
3. Connect the cables to the arc monitor located in the REB according to
the drawings.
3BHS842007 E01 REV C
Figure 6-7 Location of Arc Guard sensors in a TEU
Figure 6-8 Cable tray and cable ducts in an LSU (A = front)
(3) Cable duct for optical fibers
(4) Rail for IGCT power supply cables
of RBU, BCU and VLU
ACS6080 USER MANUAL
06 ELECTRICAL INSTALLATION
1
2
3
A
4
128/238