Data Format With Status Information For S5 - Fb 250 In Data Word; Table 26: Process Image 750-469/000-200, Type K, With Broken Wire Diagn - WAGO 750-469 Manual

2ai thermocouple 2-channel analog input module for thermocouples for wago-i/o-system 750
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-469 2AI Thermocouple
4.2
Data Format with Status Information for S5 – FB 250
in Data Word
For the 750-469/000-200 and 750-469/000-206 variations, the temperature values
of the sensors are represented with a resolution of 1 digit per 0.125 °C within a
word (16 bits). Thus, 0 °C corresponds to the numeric value 0x0000 and 100 °C to
0x0320 (dec. 800). Diagnostic information is indicated in the 3 low bits.

Table 26: Process Image 750-469/000-200, Type K, with broken wire diagn.

Temperature
°C
< ca.-100.0
-100.0
-50.0
0.0
50.0
100.0
200.0
400.0
600.0
800.0
1000.0
1200.0
1370.0
> ca.1370.0
Broken wire
1)
Status information: X: not used, F: short-circuit, broken wire, Ü: overrange
2)
Temperature values below 0 °C are represented in two's complement binary form.
Manual
Version 1.1.0
Numercial value
binary
XFÜ
'1111.1100.1101.1
001'
'1111.1100.1110.0
000'
'1111.1110.0111.0
000'
'0000.0000.0000.0
000'
'0000.0001.1001.0
000'
'0000.0011.0010.0
000'
'0000.0110.0100.0
000'
'0000.1100.1000.0
000'
'0001.0010.1100.0
000'
'0001.1001.0000.0
000'
'0001.1111.0100.0
000'
'0010.0101.1000.0
000'
'0010.1010.1101.0
000'
'0010.1010.1101.1
001'
'0111.1111.1111.1
010'
Process Image
1)
hex.
dec.
0xFCD9
-807
0xFCE0
-800
0xFE70
-400
0x0000
0
0x0190
400
0x0320
800
0x0640
1600
0x0C80
3200
0x12C0
4800
0x1900
6400
0x1F40
8000
0x2580
9600
0x2AD0
10960
> 0x2AD9
> 10969
0x7FFA
32762
33
Status-
LED
byte
Error
hex.
AI 1, 2
0x41
on
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x42
on
0x42
on