18
Device Description
3.2.3

CAGE CLAMP

Figure 3: CAGE CLAMP
Table 6: Legend for Figure "CAGE CLAMP
Channel
1
2
Only use connections 3 and 7 as a signal ground!
The current between connections 3 and 7 must be less than 0.1 A. A current
greater than 0.1 A can destroy the I/O module. Only use connections 3 and 7 as a
signal ground.
Use shielded signal lines!
Only use shielded signal lines for analog signals and I/O modules which are
equipped with shield clamps. Only then can you ensure that the accuracy and
interference immunity specified for the respective I/O module can be achieved
even in the presence of interference acting on the signal cable.
®
Connectors
®
Connectors
Designation
+TC 1
−TC 1
Common (ground)
Shield (screen)
+TC 2
−TC 2
Common (ground)
Shield (screen)
®
Connectors"
Connector Function
1
Sensor 1: +TC
2
Sensor 1: −TC
3
Common (ground)
4
Shield (screen)
5
Sensor 2: +TC
6
Sensor 2: −TC
7
Common (ground)
8
Shield (screen)
WAGO-I/O-SYSTEM 750
750-469 2AI Thermocouple