WAGO-I/O-SYSTEM 750
750-469 2AI Thermocouple
3.6
Technical Data
3.6.1
Device
Table 8: Technical Data – Device
Width
Height (from upper edge of DIN 35 rail) 64 mm
Length
Weight
3.6.2
Supply
Table 9: Technical Data – Supply
Power supply
Max. current consumption (internal)
Isolation
3.6.3
Inputs
Table 10: Technical Data – Inputs
Number of inputs
Sensor types
the free configurable variation
(750-469/003-000) supports all
listed sensor types
Manual
Version 1.1.0
Device Description
12 mm
100 mm
38.2 g
Via system voltage DC/DC
65 mA
500 V system/supply
2
Type K; −100 °C ... +1370 °C
(basic variation)
optional variations available:
type S; − 50 °C ... + 1700 °C
type T; − 100 °C ... + 400 °C
type J; − 100 °C ... + 1200 °C
type E; − 100 °C ... + 1000 °C
type L; − 100 °C ... + 900 °C
further configurable variants of 750-469/003-000:
type B; + 600 °C ... + 1800 °C
type N; − 100°C ... + 1300 °C
type R; 0 °C ... + 1700 °C
type U; − 25 °C ... + 600 °C
Voltage measurement:
− 30 mV ... + 30 mV
− 60 mV ... + 60 mV
− 120 mV ... + 120 mV
21