Process Image; Table 21: Input Bits - WAGO 750-606/040-000 Manual

Power supply 24 vdc xtr supply module; 24 vdc; extreme, for intrinsically safe xtr modules for wago i/o system 750 xtr
Table of Contents

Advertisement

WAGO I/O SYSTEM 750 XTR
750-606/040-000 Power Supply 24 VDC XTR for Ex i XTR Modules

Process Image

4
Mapping of process data in the process image of fieldbus systems
The representation of the I/O modules' process data in the process image
depends on the fieldbus coupler/controller used. Please take this information as
well as the particular design of the respective control/status bytes from the
section "Fieldbus Specific Design of the Process Data" included in the description
concerning the process image of the fieldbus coupler/controller used.

Table 21: Input Bits

S_in
0:
1:
S_out
0:
1:
24 V power supply is applied at the infeed input.
No 24 V power supply at the infeed input
24 V power supply applied to the power jumper contacts.
No 24 V power supply at the power jumper contacts;
possible causes:
Shutdown due to undervoltage of the supply
< approx. 16 V
Shutdown due to overvoltage at the output > 26.8 V
Shutdown due to overcurrent > approx. 1.2 A
Shutdown due to overtemperature
Process Image
35
Bit 1
Bit 0
S_out
S_in
Manual
Version 2.0.0

Advertisement

Table of Contents
loading

Table of Contents