The I/O module 750-606/040-000 (Power Supply 24 VDC XTR for Ex i XTR
Modules) provides 24 VDC power to the 750 XTR Series.
Furthermore, it separates the intrinsically safe part from the non-intrinsically safe
part of the fieldbus node and makes diagnostic information available in the
process image.
In the event of a short circuit or overload, electronic monitoring automatically
switches off the output voltage. After eliminating the fault, the output voltage is
reactivated within approximately ten seconds.
One green status LED indicates the status of the input voltage and one green/red
status LED indicates the status of the output voltage.
The meaning of the LEDs is described in the "Display Elements" section.
The supply module receives the 24 V voltage supply for the field level from an
external source via the CAGE CLAMP
subsequent I/O modules via the power contacts used as spring contacts.
Input and output voltages of the supply module are electrically isolated from each
other.
Do not exceed maximum current via power contacts!
The maximum current available from the "Power Supply 24 VDC Diagn for Ex i
XTR Modules" 750-606/040-000 is 1 A. Greater currents can damage the power
contacts. When configuring the system, ensure that this current is not exceeded.
If exceeded, an additional 750-606/040-000 must be used.
Keep the air and creep distances between intrinsically safe segments!
The maximum current available from the 750-606/040-000 "Power Supply
24 VDC Diagn for Ex i XTR Modules" is 1 A.
If the use of further 750-606/040-000 is necessary for reasons of extent of
utilization, 4 Separation Modules (750-616/040-000) must be used to guarantee
the distance between the intrinsically safe segments.
Installation only in zone 2 or in non-hazardous environments!
The installation of the WAGO I/O SYSTEM 750 fieldbus couplers/controllers and
I/O modules is only to be done in zone 2 or in non-hazardous environments.