64
Commissioning
Pos : 36.3 /Serie 761 (TO- PASS)/Bedi enen/Bedienen 761- 1xx/- 2xx/- 3xx Fer nabfr age per SM S - Ü bersc hrift 3 und Ei nleitung @ 13\mod_1352720644441_21.doc x @ 105907 @ 3 @ 1
6.14.1

Remote Polling via SMS

For remote polling via SMS, send an SMS containing the text "State" to the TO-
®
PASS
telecontrol module.
The TO-PASS
mobile phone containing all of the current process values.
Pos : 36.4 /Serie 761 (TO- PASS)/Bedi enen/Bedienen 761- 11x F ernabfrage SM S T abelle 4DI 4D O @ 7\mod_1272289967014_21.doc x @ 55680 @ @ 1

Table 29: SMS format

Value transmitted:
Module 1
1001
0110
Normal Status
AC=99
Pos : 36.5 /Serie 761 (TO- PASS)/Bedi enen/Bedienen 761- 11x/-21x F ernabfrag e SMS Einl eitung C I @ 13\mod_1355319867487_21.doc x @ 107520 @ @ 1
If at least one digital input is configured as a counter input, the counter status is
added to the SMS. The additional lines are added in front of the "Status text" line.
Pos : 36.6 /Serie 761 (TO- PASS)/Bedi enen/Bedienen 761- 11x/-21x/- 31x F ernabfrage SM S T abelle CI @ 13\mod_1352716526542_21.doc x @ 105854 @ @ 1
The counter status shows the last change that has occurred since the last SMS
transmission, or after a system start (independent of the value and logger status).
Example:

Table 30: Items added to SMS for counter inputs

Value transmitted
0
e34560000
C10000000
R0
The counter status may be one of the following statuses:
®
telecontrol module responds promptly with an SMS to your
Meaning
Identity
Condition of the digital inputs 1 ... 4
(0 = not set, 1 = set)
Condition of the digital outputs 1 ... 4
(0 = not set, 1 = set)
Status text or prepaid information (optional)
Alarm counter
(displays the alarms that are still possible per hour).
The alarm counter only transmitted when enabled (Alarm
counter parameter in the Identifier dialog <> "0").
Explanation
Status counter 1 (no counter)
Status counter 2 (counter active, counter value =
34560000)
Status counter 3 (counter value changed, value =
10000000)
Status counter 4 (counter reset, value = 0)