Apply the iTRAK Power Cable Shield Clamp

Factory-supplied 2198T-CHBFLS8-12AAxx iTRAK cables are shielded. The braided cable shield must terminate at the iTRAK power supply
when installed. A small portion of the cable jacket has been removed to expose the shield braid. The exposed area must be clamped by using the
clamp on the bottom front of the iTRAK power supply.
This procedure assumes that you have completed wiring your IDC and ICP connectors and are ready to apply the cable shield clamp.
To apply the iTRAK power-supply cable-shield clamp, do the following.
1. Loosen the clamp knob.
2. Position the exposed portion of each cable braid directly in line with the clamp.
3. Hand tighten the clamp knob.
Only finger-tight torque on the clamp knob is required. The cable must not move within the clamp under its own weight or when slight
pressure is applied by hand.

Install the iTRAK Bus Conditioner Module

If you have a 2198T-ExxxxxxxxxxxxxxxC iTRAK system, the bus conditioner module is already installed.
To install the iTRAK bus conditioner module, do the following.
1. Determine the location for the bus conditioner module.
We recommended that you use the pre-drilled and tapped holes on the iTRAK spine bars for mounting the bus conditioner module. If your
system configuration requires you to relocate the bus conditioner module see
2. To gain access to the bus conditioner module mounting holes, remove the cover by loosening the four screws that attach the cover to the bus
conditioner module enclosure.
These screws are captive and remain with the cover.
IMPORTANT
A ground wire connects the cover to the enclosure. When removing the cover, be careful not to stress the ground wire and do not disturb any of the
wiring or components within the bus conditioner module enclosure.
Cover Captive Screws
Four M6 x1, 30 mm long screws are shipped with the bus conditioner module. Use these screws to mount the bus conditioner module.
Rockwell Automation Publication 2198T-IN001C-EN-P - October 2019
Kinetix 5700 iTRAK Power Supply and iTRAK Bus Conditioner Module
Bus Conditioner Module Mounting Options on page
Ground Wire