Allen-Bradley 1606-XLB240E Reference Manual

Allen-Bradley 1606-XLB240E Reference Manual

Basic power supply 10 a

Advertisement

Reference Manual
Original Instructions
Basic Power Supply 10 A
Catalog Number 1606-XLB240E

Advertisement

Table of Contents
loading

Summary of Contents for Allen-Bradley 1606-XLB240E

  • Page 1 Reference Manual Original Instructions Basic Power Supply 10 A Catalog Number 1606-XLB240E...
  • Page 2: Important User Information

    Important User Information Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.
  • Page 3: Table Of Contents

    Provides declarations of conformity, certificates, and www.rockwellautomation.com/global/certification/ other certification details. overview.page You can view or download publications at http://www.rockwellautomation.com/global/literature-library/overview.page. To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative. Rockwell Automation Publication 1606-RM056A-EN-P - December 2016...
  • Page 4: Terminology And Abbreviations

    Basic Power Supply 10 A Terminology and Abbreviations Term Definition 230V AC A figure with the unit (V AC) at the end is a momentary figure without any additional tolerances included. 50 Hz vs. 60 Hz As long as not otherwise stated, AC 100V and AC 230V parameters are valid at 50 Hz mains frequency.
  • Page 5: Product Overview

    The 1606-XLB240E power supply offers these features: • Wide input range, AC 100…240V • Active PFC • Cost optimized without compromising quality or reliability.
  • Page 6: Front Side And User Elements

    Factory set: 24.1V DC-OK status indicator (green) On, when the output voltage is >18V DC-OK Relay Contact (push-in terminals) Protection Features Attribute 1606-XLB240E Output protection Electronically protected against overload, no-load, and short circuits Output overvoltage protection typ 30.5V DC In case of an internal power supply...
  • Page 7: Safety Features

    Basic Power Supply 10 A Safety Features Attribute 1606-XLB240E Input/output SELV IEC/EN 60950-1 separation PELV IEC/EN 60204-1, EN 50178, IEC 62103, IEC 60364-4-41 double or reinforced insulation Class of protection PE (Protective Earth) connection required Isolation resistance > 5 MOhm...
  • Page 8: Input

    Basic Power Supply 10 A Input Attribute 1606-XLB240E AC input 100…240V AC Auto-select, suitable for TN-, TT- and IT mains networks AC input range 90…264V AC continuous operation 264…300V AC < 500 ms Allowed voltage L or N to earth...
  • Page 9: Dc-Input

    Basic Power Supply 10 A DC-Input Do not operate the power supply with DC-input voltage. Input Inrush Current A NTC inrush limiter limits the input inrush current after turn-on of the input voltage. Attribute AC 100V AC 120V AC 230V Notes Inrush 14.5 A peak...
  • Page 10: Output

    Basic Power Supply 10 A Output Attribute 1606-XLB240E Notes Output voltage DC 24V Adjustment range 24…28V guaranteed at clockwise end position of potentiometer Factory settings 24.1V ±0.2%, at full load, cold unit Line regulation 5 mV 90…264V AC Load regulation 100 mV static value, 0A ..
  • Page 11: Hold-Up Time

    It is independent of a back-fed voltage from a unit that is connected in parallel to the power supply output such as a redundant application. Attribute 1606-XLB240E Contact closes As soon as the output voltage reaches 21.8V Contact opens As soon as the output voltage dips below 21.7V...
  • Page 12: Efficiency And Power Loss

    Basic Power Supply 10 A Efficiency and Power Loss Attribute AC 100V AC 120V AC 230V Notes Efficiency 93.2% 94.0 % 95.2 % at 24V, 10 A Average 92.7% 93.1 % 93.9 % 25% at 2.5 A efficiency 25% at 5 A 25% at 7.5 A 25% at 10 A Power losses...
  • Page 13: Lifetime Expectancy And Mean Time Between Failure (Mtbf)

    Basic Power Supply 10 A Lifetime Expectancy and Mean Time Between Failure (MTBF) Attribute AC 100V AC 120V AC 230V Notes Lifetime expectancy 89 000 h 93 000 h 103 000 h at 24V, 5 A and 40 °C (158 °F) 252 000 h 262 000 h 291 000 h...
  • Page 14: Emc

    Basic Power Supply 10 A EMC Immunity According to Generic Standards EN 61000-6-1 and EN 61000-6-2 Criterion Electrostatic EN 61000-4-2 contact discharge Criterion A discharge air discharge Criterion A Electromagnetic RF EN 61000-4-3 80MHz-2.7GHz 20V/m Criterion A field Fast transients EN 61000-4-4 input lines 4 kV...
  • Page 15: Application Notes

    Basic Power Supply 10 A Application Notes Peak Current Capability The unit can deliver peak currents (up to several milliseconds) which are higher than the specified short-term currents. This helps to start current demanding loads. Solenoids, contactors, and pneumatic modules often have a steady state coil and a pick-up coil. The inrush current demand of the pick-up coil is several times higher than the steady-state current and usually exceeds the nominal output current.
  • Page 16 Basic Power Supply 10 A Back Feeding Loads Loads such as decelerating motors and inductors can feed voltage back to the power supply. This feature is also called return voltage immunity or resistance against Back- E.M.F. (Electro Magnetic Force). This power supply is resistant and does not show malfunctioning when a load feeds back voltage to the power supply.
  • Page 17 Basic Power Supply 10 A Recommendations for building redundant power systems: – Use the DC-OK signal contact to monitor the individual power supply units. – Use separate input fuses for each power supply. – Use separate mains systems for each power supply whenever it is possible.
  • Page 18 Basic Power Supply 10 A Inductive and Capacitive Loads The unit is designed to supply any kind of loads, including capacitive and inductive loads. If extreme large capacitors, such as EDLCs (electric double layer capacitors or “UltraCaps”) with a capacitance larger than 2.0 F are connected to the output, the unit might charge the capacitor in the HiccupPLUS mode, see Output on page...
  • Page 19: Specifications

    18.8 K (1) Load is placed outside the box. (2) In the middle of the right side of the power supply with a distance of 1 cm (0.39 in.) Specifications Attribute 1606-XLB240E Notes Output Voltage 24V DC Adjustment range 24…28V DC...
  • Page 20: Environment

    Basic Power Supply 10 A Environment Attribute 1606-XLB240E Notes Operational temperature -25… +70 °C (14...158 °F) reduce output power, see Figure Storage temperature -40… +85°C (-40…185 °F) for storage and transportation Output derating 6W/°C 50°…70 °C (131…158 °F) Humidity 5...95% r.h.
  • Page 21: Dielectric Strength

    Basic Power Supply 10 A Dielectric Strength The output voltage is floating and has no ohmic connection to the ground. Type and factory tests are conducted by the manufacturer. Field tests can be conducted in the field using the appropriate test equipment, which applies the voltage with a slow ramp (2 s up and 2 s down).
  • Page 22: Standards Compliance And Certifications

    Basic Power Supply 10 A Standards Compliance and Certifications EC Declaration of Conformity The CE Marking indicates conformance with the low voltage and EMC Directive. EN 60950-1, EN 61000-6 UL 508 Listed for use as Industrial Control Equipment ;U.S.A. (UL 508) and Canada (C22.2 No.
  • Page 23: Approximate Dimensions And Weight

    Basic Power Supply 10 A Approximate Dimensions and Weight Attribute Value Width 49 mm (1.93 in.) Height 124 mm (4.88 in.) Depth 124 mm (4.88 in.) Weight 540 g (1.21 lb) DIN rail Use 35 mm DIN rails according to EN 60715 or EN 50022 with a height of 7.5 or 15 mm (0.30 or 0.59 in.). Plastic Material of Flame retardant Polycarbonate (PC) - UL94-V0 Vicat softening temperature specified with 149 °C (300 °F ) Housing...
  • Page 24 Basic Power Supply 10 A Notes: Rockwell Automation Publication 1606-RM056A-EN-P - December 2016...
  • Page 26 How Are We Doing? form at http://literature.rockwellautomation.com/idc/groups/literature/documents/du/ra-du002_-en-e.pdf. Rockwell Automation maintains current product environmental information on its website at http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page. Allen-Bradley, Rockwell Automation, and Rockwell Software are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.