Kinetix 5700 iTRAK Power Supply and iTRAK Bus Conditioner Module

Enclosure Requirements

The recommended minimum cabinet depth is 300 mm (11.81 in.).
iTRAK Power Supply Minimum Clearance Requirements
Observe these additional clearance requirements when mounting the iTRAK power supply:
• Additional clearance is required for cables and wires or the shared-bus connection system that is connected to the top of the power
supply.
• Additional clearance is required if other devices are installed above and/or below the power supply and have clearance requirements of
their own.
• Additional clearance to the left and right of the power supply is required when mounted next to noise sensitive equipment or clean
wireways.
IMPORTANT
Mount the iTRAK power supply in an upright position as shown. Do not mount the power supply on its side.
iTRAK Bus Conditioner Module Minimum Clearance Requirements
175 mm(6.9 in.) clearance in front of the bus
conditioner module for cable routing.
4
Kinetix 5700 iTRAK
Power Supply
Clearance to the left of the
power supply is not required.
See
Product Dimensions
on
page 3
for
iTRAK power supply dimensions.
Clearance left of the bus conditioner
module is not required.
Clearance right of the bus conditioner
module is not required.
66 mm(2.6 in.) clearance above of the bus
conditioner module for installation.
Rockwell Automation Publication 2198T-IN001C-EN-P - October 2019
40 mm (1.57 in.) clearance above the
power supply for airflow and installation.
Clearance to the right of the
power supply is not required.
100 mm (3.94 in.) clearance below the
power supply for airflow and installation.
Clearance back of the bus conditioner
module is not required.